47
Software data
Digital inputs
I1÷I3
-
PNP
I12
-
PNP
I4÷I9
-
Keyboard keys
Digital inputs/
encoder inputs
I10/A1
I11/B1
-
PNP inputs or bidirectional encoder
no. 1 (1 KHz)
I13/A2
-
NPN or monodirectonal encoder no.
2
(2 KHz)
Relay outputs
U1÷U5
-
Relay 5A-250 Vac.
U6
-
Relay 16A-250 Vac.
Digital outputs
U7÷U8
-
open-colletor outputs (closing to
ground if active) 20 mA max
Analog output
AQ1
-
Tension 0-5V (8 bit) 20 mA
Serial ports
COM1
-
RS485 on terminal block and
connector COM plug-8 poles (not
isolated).
IR
-
Infrared receiver for remote switch.
COM2
-
RS232 on connector COM plug-8
poles (not isolated).
1.2 Electrical wirings
Name
Description
0
Common pin for power supply 24 / 230 VAC. To improve noises
immunity, the secondary of dedicated transformer is highly
recommended
24
Supply 24 VAC. Use this pin for supply 24 VAC
230
Supply 230 VAC. Use this pin for supply 230 VAC.
F
Phase input for relay outputs. Fuse 8A - 250Vprovided for safety
N
Neutral pins of outputs.
Q1
Relay output Q1. If output is active, F signal reported on Q1
Q2
Relay output Q2. If output is active, F signal reported on Q2
Q3
Relay output Q3. If output is active, F signal reported on Q3
Q4
Relay output Q4. If output is active, F signal reported on Q4
Q5
Relay output Q5. If output is active, F signal reported on Q5
Q6
Relay output Q6. If output is active, F signal reported on Q6