![Pixsys EPL101 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/pixsys/epl101/epl101_user-manual_1560852061.webp)
61
0
filter enabled
1
filter excluded
Bit 7
Exclude software filter for analog input 4
R/W
0
filter enabled
1
filter excluded
SM39
2039
Filter on digital inputs (default 10 ms)
A filter may be applied to the signals of digital inputs
entering a delay time. If the state of input changes,
new state will be confirmed only if input will keep this
state for the given time. Data will be confirmed after
that filter will have eliminated noises and stabilized the
inputs lines.
PLC accepts delay time values between 0 and 50 ms.
R/W
SM40
2040
Configuration Analog input AI1
SM41
2041
Configuration Analog input AI2
SM42
2042
Configuration Analog input AI3
SM43
2043
Configuration Analog input AI4
These special marker words define the type of sensor
connected to analog inputs AI1, AI2, AI3 and AI4
(select properly the jumpers for configuration of
inputs).
0
Desabled
1
Input 0÷1V
2
Input 0÷20mV
3
Input 0÷20mA (AI1 only)
4
Input 4÷20mA (AI1 only)
5
Thermocouple K (only AI1..AI3)
6
Thermocouple S (only AI1..AI3)
7
Thermocouple T (only AI1..AI3)
8
Thermocouple R (only AI1..AI3)
9
Thermocouple J (only AI1..AI3)
10
Thermocouple E (only AI1..AI3)
11
Thermocouple B (only AI1..AI3)
12
Input PT100
13
Input NI100
14
Compensation PT100/NI (only AI2 + AI3)
15
NTC-10K
Ω
β
=3435
R/W
SM44
2044
Min. value for Analog input AI1 linear
SM45
2045
Min. value for Analog input AI2 linear
SM46
2046
Min. value for Analog input AI3 linear
SM47
2047
Min. value for Analog input AI4 linear
SM48
2048
Max value for Analog input AI1 linear
SM49
2049
Max value for Analog input AI2 linear