The Filtered Supply
$SSHQGL[ % 3RZHU 6XSSO\ &DOFXODWLRQV
XP Series Transponder PN 15888:G 6/11/98
57
inactive current load. A finite amount of additional current must be provided by the
power supply during an activated condition. Use Table 6 to determine the activated
load. The requirements for inactive and active current loads cannot exceed the
capabilities of the power supply in either case.
A total of 3.0 amps (internal) @ 24 VDC is available from the MPS-24A/MPS-24AE
Main Power Supply during inactive conditions. No more than 6 amps @ 24 VDC can
be drawn from the MPS-24A/MPS-24AE during active conditions (only if the XP
Transponder is in local mode). If the XP Transponder is not in local mode only, 3.0
amps may be drawn in an activated state. The MPS-24B/MPS-24BE provides 750 mA
of filtered power for system modules and 2.0 amps for notification appliances.
1RWH 7KH ;30 DQG ;3& WUDQVSRQGHU PRGXOHV GUDZ GLIIHUHQW FXUUHQW OHYHOV GHSHQGLQJ XSRQ
ZKHWKHU WKH\ DUH HPSOR\HG DV IRXUFLUFXLW RU HLJKWFLUFXLW PRGXOHV &RPSOHWH WKH IROORZLQJ WDEOHV
DFFRUGLQJO\
Table 5 Filtered Power Requirements (Not Activated) @ 24 VDC
Table 6 allows the system designer to determine the percentage of the system that
should be supported by the Main Power Supply during an activated condition. Enter the
number of circuits, by device type, that the Main Power Supply should power
simultaneously in an activated state.
1RWH 7\SLFDOO\ D V\VWHP VKRXOG EH GHVLJQHG DURXQG WKH FDSDFLW\ WR DFWLYDWH DOO RXWSXW FLUFXLWV DQG
UHOD\V DQG VXSSRUW VKRUWV RQ QR OHVV WKDQ RI ,QLWLDWLQJ 'HYLFH &LUFXLWV VXEMHFW WR WKH /RFDO $XWKRULW\
+DYLQJ -XULVGLFWLRQ
Device Type
# of
Devices
Current Draw (amps)
Total Current/
Device
MPS-24A/MPS-24AE
MPS-24B/MPS-24BE
[ ]
[ ]
X
X
0.064
0.062
=
=
APS-6R
[ ]
X
0.025
=
AVPS24/AVPS-24E
[ ]
X
0.008
=
XPP-1
[ ]
X
0.023
=
XPM-8 (Style B)
[ ]
X
0.147
=
XPM-8 (Style D)
[ ]
X
0.086
=
XPM-8L (Style B only)
[ ]
X
0.085
=
XPC-8 (Style Y)
[ ]
X
0.033
=
XPC-8 (Style Z)
[ ]
X
0.017
=
XPR-8
[ ]
X
0.004
=
4-wire smoke detectors
[ ]
X
Standby current draw
=
Listed power supervision
relays
[ ]
X
Relay current draw
=
Sum Column for Current Load
=
amps