NFPA 72 Protected Premises Fire Alarm System
$SSHQGL[ $ 1)3$ &RGH6SHFLILF 5HTXLUHPHQWV
XP Series Transponder PN 15888:G 6/11/98
51
$SSHQGL[$1)3$&RGH6SHFLILF5HTXLUHPHQWV
The Notifier XP Series Transponder is an expandable multiplex Fire Alarm Control
Panel designed for use in commercial, industrial, and institutional applications. The
XP Transponder meets the requirements for service under the National Fire Protection
Association (NFPA) Code outlined in this appendix. This appendix covers the
requirements for employing the XP Transponder as a stand-alone Fire Alarm Control
Panel under the appropriate NFPA code. The minimum system components required
for compliance with the appropriate NFPA code are listed in each area.
1)3$3URWHFWHG3UHPLVHV)LUH$ODUP6\VWHP
0LQLPXP(TXLSPHQW5HTXLUHG
•
BE-XP Basic Equipment Package which includes the Transponder Processor
Module (XPP-1), CHS-4 Chassis, and XPDP Transponder Dress Panel.
•
MPS-24A/MPS-24AE or MPS-24B/MPS-24BE Main Power Supply.
•
An XP Transponder Cabinet, Batteries (refer to Standby Power Requirements), and
BP-1 Battery Dress Panel.
•
VP-2 Vented Dress Panel.
•
XPM-8/XPM-8L Transponder Monitor Module providing Initiating Device
Circuits for connection of two (XPM-8 only) or four-wire smoke detectors, manual
pull stations, and heat detectors.
•
XPC-8 Transponder Control Module providing up to eight Style Y or four Style Z
Notification Appliance Circuits for connection of UL-listed 24 VDC alarm
notification appliances.
,QVWDOODWLRQ
This unit must be installed as outlined in Section Five (The XPM Module) and (The
XPC Module).
Set the switches on DIP switch SW1 on the XPP-1 as follows:
1RWH ,I WKH ;3 7UDQVSRQGHU LV WR EH XVHG DV D SHULSKHUDO SDQHO WR DQ )$&3 EXW LV WR IXQFWLRQ LQ DFFRUGDQFH
ZLWK 1)3$ /RFDO GXULQJ ORVV RI 6/& FRPPXQLFDWLRQ VHW ',3 VZLWFK 6: WR WKH 2)) SRVLWLRQ
OFF (stand-alone operation)*
ON (stand-alone operation)*
?
NVRAM - See Programming
ON (piezo will always sound)
?
Alarm Verification - set as desired
?
Signal Silence - set as desired
?
XPP-1 Relays - set as desired
ON Supply Supervision - (stand-alone operation)*
DIP switch SW1