![Pittway NOTIFIER AA-100 Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/pittway/notifier-aa-100/notifier-aa-100_manual_1560284051.webp)
Programming the XP Transponder for Rapid All Call Activation
3URJUDPPLQJ WKH ;3 7UDQVSRQGHU
XP Series Transponder PN 15888:G 6/11/98
47
6WHS7KUHH3URJUDPPLQJWKH;5$0
A shunt plug acts as the programming key to enter the
XRAM-1 programming mode. Its storage position is at JP1
and JP2 on the XPP-1, where it straddles both jumpers.
1RWH 7KH 7UDQVSRQGHU ZLOO QRW IXQFWLRQ DV D ILUH DODUP FRQWURO SDQHO
ZKLOH WKH ;5$0 LV EHLQJ SURJUDPPHG
To enter the programming mode:
1. Place the programming key over the pins of JP3, then
push and release the RESET switch.
2. Remove the programming key and return it to its storage
position.
The green AC Power LED on the XPP-1 will flash to indicate
that the XPP-1 is now in program mode. The XRAM-1 has a
default program that automatically maps each initiating device circuit to all output/relay
circuits. To modify this default program, select an initiating circuit on an XPM-8 for
mapping by shorting the positive (+) terminal to a negative (-) terminal of that circuit.
The initiating circuit’s LED will illuminate (two LEDs for Style D wired circuits). All
output/relay circuits that are currently mapped to this circuit will be indicated by
illuminated green LEDs.
Outputs are mapped (or unmapped) to the selected initiating circuit by shorting the
positive (+) and negative (-) terminals of the notification circuits, or by shorting relay
jumper pins J1 through J8 of the XPR-8 or JP1 and JP2 of the XPP-1. The initiating
circuit’s LED will flash with the first change made to the programming map. An output
circuit will change state (from mapped to unmapped, or unmapped to mapped) each
time it is shorted.
After mapping the initiating circuit, push the RESET switch to store the programming.
All LEDs on the XP Transponder will turn off except the LEDs on the XPP-1.
Repeat this procedure for all initiating circuits that require mapping.
1RWH ;3 7UDQVSRQGHU FLUFXLWV GR QRW KDYH WR EH SURJUDPPHG LQ VHTXHQWLDO IDVKLRQ 7KH\ FDQ EH
SURJUDPPHG DQG UHSURJUDPPHG LQ DQ\ RUGHU +RZHYHU DIWHU HDFK FLUFXLW LV SURJUDPPHG WKH
SURJUDPPLQJ VKRXOG EH VWRUHG E\ SUHVVLQJ WKH UHVHW EXWWRQ
The user may exit programming mode by placing the programming key over the
programming pins (JP3) and pressing the reset button on the XPP-1. Remove the
programming key and return it to its storage position.
1RWH 3URJUDP PRGH ZLOO WLPH RXW DIWHU WZR PLQXWHV RI LQDFWLYLW\
'HIDXOW3URJUDPPLQJ
Any initiating circuit that is not individually programmed will retain a default mapping.
This default program maps each initiating circuit to every output circuit and relay,
except XPP-1 relays.
3URJUDPPLQJWKH;37UDQVSRQGHUIRU5DSLG$OO&DOO$FWLYDWLRQ
(For use in AM2020/AFP-1010 Audio Systems only)
1RWH 7KH 5DSLG $FWLYDWLRQ $OO &DOO IHDWXUH UHTXLUHV UHOHDVH DQG KLJKHU RU 0 DQG KLJKHU
VRIWZDUH DQG ;33 VRIWZDUH FKLS RU ODWHU LQ WKH $0$)3
The Rapid Activation All Call feature can be used in any mode of operation except
local mode. To enable this feature, enter the program mode as described in
"Programming the XRAM-1" above. Once in the program mode, ensure that all LEDs
on the XP Transponder are off with the exception of the XPP-1 LEDs. (If LEDs other
than those on the XPP-1 are on, review "Programming the XRAM-1" section.)
3URJUDPPLQJ .H\ 6WRUDJH
3RVLWLRQ VWUDGGOLQJ -3 DQG -3
-3
-3
3URJUDPPLQJ .H\
3URJUDPPLQJ (QDEOHG .H\
3RVLWLRQ FRYHULQJ -3 SLQV
-3
3URJUDPPLQJ .H\