![Pittway NOTIFIER AA-100 Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/pittway/notifier-aa-100/notifier-aa-100_manual_1560284054.webp)
2SHUDWLQJ WKH ;3 7UDQVSRQGHU
Acknowledging Troubles
50
XP Series Transponder PN 15888:G 6/11/98
the flashing Trouble LED. If more than one trouble exists in one XP Transponder
system (row), the trouble LED will annunciate each error sequentially, and repeat the
procedure until each trouble has been cleared. See Appendix C: Troubleshooting the
XP Transponder for error codes.
$FNQRZOHGJLQJ7URXEOHV
Press the Acknowledge/Silence/Reset Button momentarily. Do not hold in for more
than five seconds or the Transponder will be reset. Each trouble in the system must be
acknowledged individually. If the particular trouble being acknowledged is due to a
fault on an IDC or NAC (Field Trouble), the XP Transponder will momentarily light the
LED of the circuit(s) in trouble. After all troubles have been acknowledged, the piezo
sounder will be silenced (if enabled, otherwise it will never sound). The trouble LED
will continue to flash the codes of troubles that still exist. Once each trouble is cleared,
the Transponder will stop flashing the associated trouble code.