Pionetics LINX 140T Скачать руководство пользователя страница 18

Consumer Install 12.16.2016 

18

for the LINX 100 TDS cartridge replacement procedure. The optional LED-UV lamp is designed to operate for the life of the 
LINX 140T system. 
 

5.2

 

  Indicator Light Alarm 

There are five conditions which prevent operation (water flow):   

 

1.

 

Blue safety lid covers not properly positioned 

2.

 

Drain line plugged 

3.

 

External Leak 

4.

 

No power to LINX cells (no TDS reduction) 

 

Refer to the bottom of the Indicator Light Status Table in Section 4, Operation, for details.    To correct the lid cover alarm, the lids 
must be installed as shown at the beginning of Section 4.    To clear the drain plug, drain leak, no power or external leak alarms 
repower the system – unplug it, wait 15 seconds and plug it back in.    The lights will flash.    If these alarms occur again after 
re-powering, service is required. 
 
HARD WATER 
When treating hard water, scale will accumulate in the drain valves or line and will eventually plug them.    The LINX systems 
detect drain plugging which prevents proper regeneration and provides poor TDS reduction.    LINX systems will automatically 
alarm and shutdown if inadequate drain water volume is detected.    This condition could also be caused by loss of feed pressure.   
The  LINX  system  will  open  the  valves  every  20  minutes  to  determine  if  pressure  has  been  restored  (flow  has  resumed),  and 
automatically disable the alarm if this is the case. 
 
When operating on hard water, the LINX system’s drain valves and plumbing must be periodically inspected and cleaned to avoid 
drain  line  clogging  with  scale.    The  high  water  recovery  of  LINX  systems  means  that  the  waste  water  contains  a  very  high 
concentration of hard water ions that promote scale formation in the drain line and in particularly in the drain valves.    Refer to 
Section 5.5 for Drain Line Maintenance instructions.     
 
LEAKS 
Two  sensors  mounted  on  the  base  of  the  LINX  140T  systems  detect  water  leaks.    A  light  indicator  and  beeper  indicate  this 
external leak alarm, and the feed valves immediately close, shutting off water to the majority of the LINX system.    Because the 
feed valves are located after the sediment filter and first flow sensor, a leak from these components will not be stopped.         
 

5.3 LINX Sediment and Carbon Filter Replacement Procedure 
 

Replace and rinse the Carbon filter BEFORE replacing/pre-conditioning the LINX TDS cartridges 

 

Before unplugging the system, depressurize it by closing the feed water line valve and then opening the faucet until water 
stops flowing.    If servicing a LINX 140T system, close the tank valve. 

 

Unplug the LINX system. 

 

Remove the blue front panel from the LINX system.    The two securing screws are located at the bottom. Press the white 
enclosure plastic just behind the blue enclosure down and pull forward on the front panel. 

 

Remove the front filter housing (sediment) with the filter housing wrench.    The housing is removed with clockwise rotation.   
Next remove the rear right filter housing (carbon). 

 

Discard the old (used) LINX Sediment and Carbon filters, and replace with the new components AFTER removing all shrink 
wrap covering.     

Содержание LINX 140T

Страница 1: ...l Software 20 067 Owner s Manual For service related questions call 866 611 8624 between 8 00 am and 4 30 pm Pacific time If you have problems at other times then turn off the feed water and unplug th...

Страница 2: ...ecting Feed Water TDS Level Pre Conditioning Procedure System Operation Dial A Taste Mineral Level Control Indicator Lights Section 5 Maintenance LINX TDS LINX Sediment and LINX Cartridges Filters Dra...

Страница 3: ...nstalled These systems are not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given super...

Страница 4: ...maximum TDS of 1000 ppm 20 grains of hardness 340 ppm hardness as CaCO3 pH 4 10 microbiologically safe Feed Water Pressure 20 80 psi 130 550 kPa Feed Water and Operating Temperature 33 100 F 1 40 C Re...

Страница 5: ...tain that you can reach the faucet under the sink to tighten it and connect the tubing Before you start your install the system 1 Buy an RO Faucet for your LINX System and slide the decorative plate o...

Страница 6: ...the right sized T Fitting or Angle Stop available it will be either a 1 4 3 8 or 1 2 inch outside diameter with a 1 4 inch T for the tubing that supplies the water to the LINX system 8 Determine wher...

Страница 7: ...to your cold water supply line Inline Shut off valve Heavy duty scissors Teflon plumber s tape Vaseline Plumber s Tape Tank Shut Off Valve This diagram illustrates plumbing connections using an air g...

Страница 8: ...dishwasher air gap Feed water is provided from the cold water supply under the sink via an Angle Stop on the cold water valve Do not use a saddle valve with puncturing needle because it will not prov...

Страница 9: ...hole in the tail piece so draining is not obstructed Installing the LINX system waste line to the drain below the horizontal arm of the P trap drain outlet where the P trap is full of water will lead...

Страница 10: ...d If you have a granite counter top you may want to hire someone to drill the hole for you 3 Locate where you want to put the LINX system and the storage tank under the sink ensuring a 110V Electrical...

Страница 11: ...round the filters and return the filters into their respective filter housings The Sediment Filter can be inserted into the housing in either direction but the Carbon Filter needs to be inserted with...

Страница 12: ...led 10 Locate the two LINX TDS cartridges see Figure 9 Then locate and lift out the two Lid Drivers from the exposed LINX unit see Figure 10 to identify these parts and location 11 Slide the mushroom...

Страница 13: ...ides the technician with a complete system diagnosis and IF service is needed walks the technician through the step by step service process If you would like to purchase an FSA please call Tech Suppor...

Страница 14: ...ed in the Front Panel Button Operation table below the left two lights flash three times if set for low TDS and the right two lights flash three times if set for high TDS The two buttons required for...

Страница 15: ...1000 High 0 15 gpm Yellow 1000 1500 High 0 15 gpm Yellow TDS Reduction may be less than 85 above 1000 ppm TDS feed Pre Conditioning LINX TDS Sediment and Carbon Cartridges Filters Whenever powered th...

Страница 16: ...ter is always available the LINX systems are designed for intermittent not continuous use To obtain the specified 85 TDS reduction the systems must be configured as described in the Specification sect...

Страница 17: ...urning the dial clockwise increases mineral content As the dial is turned the blue and red LEDs will light up for several seconds to indicate the mineral level selected None of the four LEDs will ligh...

Страница 18: ...and plumbing must be periodically inspected and cleaned to avoid drain line clogging with scale The high water recovery of LINX systems means that the waste water contains a very high concentration of...

Страница 19: ...ly depressurized Depressurize the system and try again open the faucet to drain all water Remove the LINX TDS cartridges from both the front and back cells The LINX TDS cartridges will come out with t...

Страница 20: ...ithin 4 seconds on the front circuit board until indicator light C blinks three times This informs the LINX system that new LINX TDS cartridges have been installed and resets the volume counter for th...

Страница 21: ...y If occurs again after re powering call Pionetics No Product Water Flow Indicator lights B C and D flashing Lid safety switch es not triggered Remedy Assure that both lid covers blue are in the prope...

Страница 22: ...00037 A LINX TDS Cartridge bottom o ring 28 00025 A LINX cell lid drivers 19 000001 C Front Enclosure 07 000008 Front Lid Cover 07 000012 Back Lid Cover 07 000013 Drain Valve Body Left from rear 19 00...

Страница 23: ...Consumer Install 12 16 2016 23...

Отзывы: