TECHNICAL MANUAL MT044
28
Settings of in-line apparatuses consisting of Regulator
+ Slam-shut + Relief valve
TAB. 7:
Regulator set-point
Set-point
Set-point
Set-point
(Pas) mbar
RELIEF VALVE
SLAM-SHUT Max
SLAM-SHUT Min
8<Pas
≤
12
12<Pas
≤
15
15<Pas
≤
19
19<Pas
≤
24
24<Pas
≤
30
30<Pas
≤
60
60<Pas
≤
80
80<Pas
≤
110
110<Pas
≤
200
200<Pas
≤
400
400<Pas
≤
800
800<Pas
≤
1000
1000<Pas
≤
2500
2500<Pas
≤
4000
20 mbar
Pas x 1.5
Pas x 1.4
Pas x 1.25
Pas x 1.15
25 mbar
Pas + 20 mbar
Pas + 30 mbar
Pas + 40 mbar
Pas + 100 mbar
Pas + 150 mbar
Pas + 300 mbar
Pas + 500 mbar
Pas + 1000 mbar
Slam-shut not
available
10 mbar
Pas -10 mbar
Pas -20 mbar
Pas -40 mbar
Pas -60 mbar
Pas -100 mbar
Pas -200 mbar
Pas -300 mbar
Содержание NORVAL
Страница 2: ...TECHNICAL MANUAL MT044 2 Inlet pressure Outlet pressure NORVAL Issue February 2003 ...
Страница 4: ...4 ...
Страница 8: ...8 ...
Страница 10: ...TECHNICAL MANUAL MT044 10 5 Pe 4 1 3 2 74 Pa Fig 1 ...
Страница 36: ...TECHNICAL MANUAL MT044 36 7 2 NORVAL REGULATOR MAINTENANCE PROCEDURE Fig 17 ...
Страница 39: ...TECHNICAL MANUAL MT044 39 7 3 NORVAL REGULATOR I N MAINTENANCE PROCEDURE Fig 18 ...
Страница 43: ...TECHNICAL MANUAL MT044 43 7 4 MAINTENANCE PROCEDURE FOR THE NORVAL REGULATOR I N ER Fig 19 ...
Страница 50: ...TECHNICAL MANUAL MT044 50 9 0 LIST OF RECOMMENDED SPARE PARTS ...
Страница 51: ...TECHNICAL MANUAL MT044 51 NORVAL pression regulator ...
Страница 58: ...TECHNICAL MANUAL MT044 58 NOTES ...
Страница 59: ...TECHNICAL MANUAL MT044 Ordering Information Part No PFN375DN50 40 PFN375DN50 45 ...