TECHNICAL MANUAL MT044
18
The modular-type conception of NORVAL series regulators means that it is also possible to fit the slam-shut
incorporated with the body itself even after the installation of the regulator.
Furthermore, the regulator can be adapted for operation as an in-line monitor by installing a special device.
4.1
INCORPORATED SLAM-SHUT I-N
This is a device (fig. 7) which immediately blocks the gas flow if, following some kind of failure, the downstream
pressure reaches the set-point for its intervention or if it is operated manually.
The main characteristics of the slam-shut device are:
• design pressure: 18.9 bar for all the components;
• intervention with pressure increase and/or decrease;
• intervention accuracy (AG): ± 1% of the pressure set-point for pressure increases, ± 5% for pressure decreases;
• incorporated by-pass for balancing the pressures and facilitating the resetting of the device.
• push-button manual control.
4.0
MODULARITY
...+ I-N SLAM-SHUT
Fig. 7
Содержание NORVAL
Страница 2: ...TECHNICAL MANUAL MT044 2 Inlet pressure Outlet pressure NORVAL Issue February 2003 ...
Страница 4: ...4 ...
Страница 8: ...8 ...
Страница 10: ...TECHNICAL MANUAL MT044 10 5 Pe 4 1 3 2 74 Pa Fig 1 ...
Страница 36: ...TECHNICAL MANUAL MT044 36 7 2 NORVAL REGULATOR MAINTENANCE PROCEDURE Fig 17 ...
Страница 39: ...TECHNICAL MANUAL MT044 39 7 3 NORVAL REGULATOR I N MAINTENANCE PROCEDURE Fig 18 ...
Страница 43: ...TECHNICAL MANUAL MT044 43 7 4 MAINTENANCE PROCEDURE FOR THE NORVAL REGULATOR I N ER Fig 19 ...
Страница 50: ...TECHNICAL MANUAL MT044 50 9 0 LIST OF RECOMMENDED SPARE PARTS ...
Страница 51: ...TECHNICAL MANUAL MT044 51 NORVAL pression regulator ...
Страница 58: ...TECHNICAL MANUAL MT044 58 NOTES ...
Страница 59: ...TECHNICAL MANUAL MT044 Ordering Information Part No PFN375DN50 40 PFN375DN50 45 ...