![PIETRO FIORENTINI 30051 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/pietro-fiorentini/30051/30051_operation-and-maintenance-manual_1555774041.webp)
41
GOVERNORS NOR
TH AMERICA
LOW PRESSURE GAS REGULATOR
|
DESCRIPTION AND OPERATION
|
REV. A
US
Operation, maintenance and warning manual
In Tab. 4.22 flow rate values are given for each model as a function of set point and inlet pressure:
Flow rate in Scfh with filter (flow rate without filter in brackets)
Model
Set point
outlet pressure
Operating inlet pressure
14”WC
1 psig
2 psig
31051 ½”
8”WC
386 (360)
552 (649)
785 (923)
11”WC
218 (256)
511 (601)
785 (923)
31052 ¾”
8”WC
369 (450)
665 (812)
946 (1154)
11”WC
363 (321)
616 (751)
946 (1154)
31053 1”
8”WC
495 (585)
893 (1,055)
1270 (1154)
11”WC
353 (417)
825 (977)
1270 (1154)
31150 ½”
High Capacity
8”WC
610 (855)
1097 (1,543)
1558 (2193)
11”WC
433 (609)
10,14 (1,428)
1558 (2193)
31151 ¾”
High Capacity
8”WC
714 (1,080)
1284 (1,949)
1824 (2771)
11”WC
507 (770)
1187 (1,803)
1824 (2771)
31152 1”
High Capacity
8”WC
903 (1,283)
1625 (2,314)
2309 (3290)
11”WC
642 (914)
1503 (2,142)
2309 (3290)
31153 1¼”
8”WC
2,071(3,062)
3,735 (5,522)
5311 (7851)
11”WC
1,476 (2,183)
3,457 (5,110)
5311 (7851)
31154 1½”
8”WC
2,567 (3,197)
4,629 (5,766)
6581 (8197)
11”WC
1,829 (2,279)
4,284 (5,336)
6581 (8197)
31155 2”
8”WC
5,179 (5,854)
9,339 (10,557)
13278 (15009)
11”WC
3,691(4,173)
8,643 (9,336)
13278 (15009)
31156/F 2½”
8”WC
6,530 (7,431)
11,775 (13,999)
16741(19051)
11”WC
4,655 (5,297)
10,898 (12,401)
16741(19051)
31157/F 3”
8”WC
7,205 (9,007)
12,993 (16,242)
18473 (23092)
11”WC
12,025 (6,240)
12,025 (15,032)
18473 (23092)
31158/F 4”
8”WC
12,835 (15,762)
23,245 (28,424)
32906 (40411)
11”WC
9,149 (11,236)
21,420 (26,306)
32906 (40411)
Tab. 4.22.
Содержание 30051