4.5 - TECHNICAL/FUNCTIONAL FEATURES
Refer to CSA 6.22-2011/ANSI Z21.80, CSA 6.18-2002 (R2013), ANSI B109.4-1998 (R2008) for functional per-
formance classification of the equipment.
The main specifications are shown in Tab.4.19:
Technical/functional features
Design pressure (DP)
Standard Version 0.05 MPa
Ratio Version
Zero Version
0.035 MPa
Goval Version 0.1 MPa
Ambient temperature of use
Standard Version
Goval Version
-5 °F to +140 °F
Ratio Version
Zero Version
14 °F to +140 °F
Inlet pressure range
Standard Version Wd+0.25 kPa to 50 kPa
Ratio Version
Zero Version
Wd +2 kPa to 35 kPa
Goval Version Wd+0.75 kPa to 100 kPa
Downstream pressure regulation
range
Standard Version
Goval Version
0.5 kPa to 30 kPa
Ratio Version 0.2 kPa to 15 kPa
Zero Version -0.5 kPa to 0.5 kPa
Accessories
• Built-in inlet filter.
• Inlet and outlet pressure taps.
• Vent limiter.
Accuracy class (AC)
up to 15
Closure overpressure (SG)
up to 30 (minimum 0.75 KPa - 7.5 mbar)
Flow rate coefficients
Refer to Tab.4.21 and Tab.4.22 in section 4.5.1
Modular connections
• Gas (according to UNI EN ISO 228-1:2003).
• Flat swivel (according to NF E29-533: 2014 and NF E29-536:
2017).
• NPT (according to ASME B1.20.1, excluding metal-to-metal seal
connections).
• Specials (on request).
Tab. 4.19.