background image

PSI-MOS-RS232/FO 1300 E

103266_en_02

PHOENIX CONTACT

7 / 17

5

Safety regulations and installation notes

5.1

Installation notes

The category 3 device is suitable for installation in 

Zone 2 potentially explosive areas. It meets the require-

ments of EN 60079-0:2012+A11:2013 and EN 60079-

15:2010.

Installation, operation, and maintenance may only be 

carried out by qualified electricians. Follow the installa-

tion instructions as described. When installing and op-

erating the device, the applicable regulations and 

safety directives (including national safety directives), 

as well as the general codes of practice, must be ob-

served. The safety data is provided in the packing slip 

and on the certificates (conformity assessment, addi-

tional approvals where applicable).

The device must not be opened or modified apart from 

the configuration of the DIP switches. Do not repair the 

device yourself; replace it with an equivalent device in-

stead. Repairs may only be carried out by the manufac-

turer. The manufacturer is not liable for damage 

resulting from non-compliance.

The IP20 degree of protection (IEC 60529/EN 60529) of 

the device is intended for use in a clean and dry envi-

ronment. Do not subject the device to mechanical 

and/or thermal loads that exceed the specified limits.

This device is not designed for use in atmospheres with 

a risk of dust explosions.

The switches of the device that can be accessed may 

only be actuated when power to the device is discon-

nected.

The device is only intended for operation with SELV ac-

cording to IEC 60950/EN 60950/VDE 0805. The device 

may only be connected to devices that meet the re-

quirements of EN 60950.

5.2

Installation in zone 2

Observe the specified conditions for use in potentially 

explosive areas!

Install the device in a suitable, approved housing (with 

at least IP54 protection) that meets the requirements of 

EN 60079-15. For this purpose, observe the require-

ments of IEC 60079-14 / EN 60079-14.

Only connect devices to the supply and signal circuits in 

zone 2 that are suitable for operation in Ex zone 2 and 

for the conditions at the installation location.

In potentially explosive areas, only snap the device onto 

or off the DIN rail connector and connect/disconnect ca-

bles when the power is disconnected.

The device must be stopped and immediately removed 

from the Ex area if it is damaged, was subjected to an 

impermissible load, stored incorrectly or if it malfunc-

tions.

Connection to the D-SUB interface is only permitted if 

the screw connection is tightened.

5.3

UL notes

WARNING:

Observe the following safety notes when using 

the FO converter.

WARNING: Explosion hazard when used in 

potentially explosive areas

Make sure that the following notes and instruc-

tions are observed.

Содержание PSI-MOS-RS232/FO 1300 E

Страница 1: ...within a modular star coupler occurs automatically via the backplane The system supports progressive transmis sion speeds from 4 8 kbps to 115 2 kbps The devices are also equipped with comprehensive...

Страница 2: ...res 10 9 Configuration 11 9 1 Operation in a point to point connection DIP 1 11 9 2 Operation in a star structure DIP 1 11 9 3 Connection to fiber optic interfaces from third party suppliers DIP 2 12...

Страница 3: ...40AC 24DC 1 5 2866983 1 Power supply unit for use in zone 2 potentially explosive areas ATEX MINI PS 100 240AC 24DC 1 5 EX 2866653 1 End bracket CLIPFIX 35 3022218 50 DIN rail connector power supply a...

Страница 4: ...dBm 62 5 125 m multi mode fiberglass 3 4 dBm 50 125 m multi mode fiberglass Receiver sensitivity Minimum single mode fiberglass Minimum multi mode fiberglass Maximum both fibers 26 5 dBm 25 5 dBm 0 d...

Страница 5: ...Ex nA nC IIC T4 Gc X UL 508 listed 508 recognized Conformity with EMC Directive 2014 30 EU Immunity test according to EN 61000 6 21 Electrostatic discharge ESD Air discharge Contact discharge EN 6100...

Страница 6: ...in mm D SUB COMBICON 24V 1 11 3 12 4 Alarm DC DC gn DIN rail connector 24 V 0 V GND Data A Data B Bus management Function TD RD Fiber optic port Broken fiber rd ERR A Fiber optic diagnostics port A y...

Страница 7: ...mits This device is not designed for use in atmospheres with a risk of dust explosions The switches of the device that can be accessed may only be actuated when power to the device is discon nected Th...

Страница 8: ...6 2 Star structures You can network addressable RS 232 devices within a star structure as a master slave network Depending on the number of star lines required several terminal devices are connected t...

Страница 9: ...ED 9 Slide switch for DTE DCE adaptation 10 FO SIGNAL LED 11 FO SIGNAL LED 12 FO SIGNAL LED 13 ERR LED 14 Fiber optic transmitter 15 Fiber optic receiver Diagnostic and status indicators Des Color Mea...

Страница 10: ...4 Port assignment for point to point connections 8 2 Port assignment for star structures By means of full duplex mode the electrical interface com municates with all connected fiber optic ports of th...

Страница 11: ...s 9 2 Operation in a star structure DIP 1 Devices in the star coupler topology For each device in the star coupler topology set DIP 1 to ON STAR Devices at the end of a star line No further settings a...

Страница 12: ...IP 6 to ON multi mode for operation on a multi mode fiberglass 50 125 m or 62 5 125 m Leave DIP 6 set to OFF single mode for operation on a single mode fiberglass 9 125 m factory setting If you are no...

Страница 13: ...must be hooked onto the top edge of the DIN rail see Figure 9 Make sure that it is aligned correctly with the DIN rail connectors Once the device has been snapped on properly check that it is fixed se...

Страница 14: ...use in zone 2 Devices that are installed in zone 1 must not be connected to the fi ber optic interface Area with a danger of dust explosions The device is not designed for installation in areas with a...

Страница 15: ...t de vice in a topology A second power supply unit can be used to create a redundant supply concept 11 2 Connecting the data cables Connect the RS 232 connection via the D SUB 9 pin strip on the top o...

Страница 16: ...he device is equipped with a floating switching output for error diagnostics terminals 3 11 and 4 12 The switch contact opens on the relevant device in the event of the following Supply voltage failur...

Страница 17: ...tter at device 1 Fiber connection RD receiver at device 2 WARNING Danger of eye injuries During operation do not look directly into the transmitter diodes or use optical aids to look into the fibergla...