Connection to fiber optic interfaces from third-

party suppliers (DIP 2)

Check the idle setting for the third-party interface:

Logic 1 = Light off or

Logic 1 = Light on

If necessary, adjust the idle setting of PSI-MOS using DIP 2.

9.4

Switches with no function (DIP 3, 4, and 5)

These switches are currently without function. They are re-

served for later additional functions.

9.5

Adjusting the transmission power (DIP 6)

If you use multimode fiberglass cables, you can adjust the 

transmission power via DIP switches.

Set DIP 6 to "ON" (multi-mode) for operation on a multi-

mode fiberglass (50/125 µm or 62.5/125 µm).

Leave DIP 6 set to "OFF" (single mode) for operation on 

a single mode fiberglass (9/125 µm) (factory setting).

If you are not sure which type of fiberglass is used in your 

projects, contact your cable supplier.

DIP 2

Idle setting

Meaning

OFF = INVERS

Light on

1

1

Default setting

Logic 1

ON = NORM

Light off

Logic 1

If you switch DIP 2 to "ON," the FO diagnos-

tics are not available via the LED bar graph.

The LED bar graph can light up at high trans-

mission speeds or flash at low transmission 

speeds. This display does 

not

 correspond to 

continuous evaluation of the optical power.

When connecting third-party devices, ob-

serve the receiver sensitivity and overrange 

limits of the fiber optic interfaces.

Содержание PSI-MOS-RS232/FO 1300 E

Страница 1: ...within a modular star coupler occurs automatically via the backplane The system supports progressive transmis sion speeds from 4 8 kbps to 115 2 kbps The devices are also equipped with comprehensive...

Страница 2: ...res 10 9 Configuration 11 9 1 Operation in a point to point connection DIP 1 11 9 2 Operation in a star structure DIP 1 11 9 3 Connection to fiber optic interfaces from third party suppliers DIP 2 12...

Страница 3: ...40AC 24DC 1 5 2866983 1 Power supply unit for use in zone 2 potentially explosive areas ATEX MINI PS 100 240AC 24DC 1 5 EX 2866653 1 End bracket CLIPFIX 35 3022218 50 DIN rail connector power supply a...

Страница 4: ...dBm 62 5 125 m multi mode fiberglass 3 4 dBm 50 125 m multi mode fiberglass Receiver sensitivity Minimum single mode fiberglass Minimum multi mode fiberglass Maximum both fibers 26 5 dBm 25 5 dBm 0 d...

Страница 5: ...Ex nA nC IIC T4 Gc X UL 508 listed 508 recognized Conformity with EMC Directive 2014 30 EU Immunity test according to EN 61000 6 21 Electrostatic discharge ESD Air discharge Contact discharge EN 6100...

Страница 6: ...in mm D SUB COMBICON 24V 1 11 3 12 4 Alarm DC DC gn DIN rail connector 24 V 0 V GND Data A Data B Bus management Function TD RD Fiber optic port Broken fiber rd ERR A Fiber optic diagnostics port A y...

Страница 7: ...mits This device is not designed for use in atmospheres with a risk of dust explosions The switches of the device that can be accessed may only be actuated when power to the device is discon nected Th...

Страница 8: ...6 2 Star structures You can network addressable RS 232 devices within a star structure as a master slave network Depending on the number of star lines required several terminal devices are connected t...

Страница 9: ...ED 9 Slide switch for DTE DCE adaptation 10 FO SIGNAL LED 11 FO SIGNAL LED 12 FO SIGNAL LED 13 ERR LED 14 Fiber optic transmitter 15 Fiber optic receiver Diagnostic and status indicators Des Color Mea...

Страница 10: ...4 Port assignment for point to point connections 8 2 Port assignment for star structures By means of full duplex mode the electrical interface com municates with all connected fiber optic ports of th...

Страница 11: ...s 9 2 Operation in a star structure DIP 1 Devices in the star coupler topology For each device in the star coupler topology set DIP 1 to ON STAR Devices at the end of a star line No further settings a...

Страница 12: ...IP 6 to ON multi mode for operation on a multi mode fiberglass 50 125 m or 62 5 125 m Leave DIP 6 set to OFF single mode for operation on a single mode fiberglass 9 125 m factory setting If you are no...

Страница 13: ...must be hooked onto the top edge of the DIN rail see Figure 9 Make sure that it is aligned correctly with the DIN rail connectors Once the device has been snapped on properly check that it is fixed se...

Страница 14: ...use in zone 2 Devices that are installed in zone 1 must not be connected to the fi ber optic interface Area with a danger of dust explosions The device is not designed for installation in areas with a...

Страница 15: ...t de vice in a topology A second power supply unit can be used to create a redundant supply concept 11 2 Connecting the data cables Connect the RS 232 connection via the D SUB 9 pin strip on the top o...

Страница 16: ...he device is equipped with a floating switching output for error diagnostics terminals 3 11 and 4 12 The switch contact opens on the relevant device in the event of the following Supply voltage failur...

Страница 17: ...tter at device 1 Fiber connection RD receiver at device 2 WARNING Danger of eye injuries During operation do not look directly into the transmitter diodes or use optical aids to look into the fibergla...

Отзывы: