Each PROFIBUS device is equipped with an electronic name plate for unique identification.
This nameplate can be accessed, for example, during startup or for maintenance purposes.
Depending on the selected I & M function, either only read or read/write access is possible.
The following I & M function are supported:
Index 255:
Identification & Maintenance functions
Function:
Read and write I & M functions
Access:
Read and write
Length:
64 bytes
Note:
Only possible via DP/V1
For this object, each access attempt - read or write - should be implemented in two stages
(in accordance with specification IEC 61158-6, Section 6.1).
Table B-1
I & M functions (basic data)
I & M basic data
Access
Description
Header
Manufacturer specification
Read
IL PB BK DIO
I & M block
MANUFACTURER_ID
Read
Manufacturer identification Phoenix Contact = 00B0
hex
ORDER_ID
Read
Terminal order number
SERIAL_NUMBER Read
Production
serial number for unique identification
HARDWARE_REVISION
Read
Revision of hardware XXXX
hex
SOFTWARE_REVISION
Read
Version of software XXXX
hex
REVISION_COUNTER
Read
Number of modified versions XXXX
hex
PROFILE_ID
Read
F600
hex
PROFILE_SPECIFIC_TYPE
Read
0003
hex
IM_VERSION
Read
0101
hex
IM_SUPPORTED
Read
001F
hex
Tabelle 0-1
I & M functions (option)
I & M1 (option)
Access
Description
Header
Manufacturer specification
Read
IL PB BK DIO
I & M block
TAG_FUNNCTION
Read/write
Specify a system-wide unique identification for the terminal here.
TAG_LOCATION
Read/write
Enter the installation location of the terminal here.
Содержание IL PB BK DI8 DO4/EF-PAC