Diagnostics
7725_en_01
PHOENIX CONTACT
2-9
Block 2: Status PDU
A distinction is made between the following status types (byte 8):
2.1.3
ID-specific diagnostic format
This diagnostic format consists of the following blocks:
1
PROFIBUS standard diagnostics (see also 2.1.1 on page 2-2)
2
ID-specific diagnostics (see also 2.1.1 on page 2-6)
A1
hex
PROFIsafe F-Parameter error (see also Appendix A3)
A2
hex
PROFIsafe iParameter error
A3
hex
PROFIsafe device error
81
hex
Standard
status
message
Byte 11 and byte 12 provide more detailed information on the standard status message:
High byte
Error type
Low byte
Error number
For error descriptions, please refer to Section 2.2, "Representing the error codes",
Section A 3, "Error codes for F-Parameters" or the documentation of the individual
module.
Table 2-8
ID-specific (terminal) diagnostics
Byte X
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Meaning
Block 1
1
X
X
X
X
X
X
X
X
Station status 1
2
X
X
X
X
X
X
X
X
Station status 2
3
X
X
X
X
X
X
X
X
Station status 3
4
X
X
X
X
X
X
X
X
PROFIBUS master address
5
0
0
0
0
1
0
1
1
Manufacturer ID high byte (0B
hex
)
6
0
1
0
1
0
0
0
0
Manufacturer ID low byte (50
hex
)
Block 2
7
0
1
X
X
X
X
X
X
Number of devices (values 0 to 63)
8
X
X
X
X
X
X
X
X
Terminals 1 to 8 (values 0 to 255)
9
X
X
X
X
X
X
X
X
Terminals 9 to 16 (values 0 to 255)
10
X
X
X
X
X
X
X
X
Terminals 17 to 24 (values 0 to 255)
11
X
X
X
X
X
X
X
X
Terminals 25 to 32 (values 0 to 255)
12
X
X
X
X
X
X
X
X
Terminals 33 to 40 (values 0 to 255)
13
X
X
X
X
X
X
X
X
Terminals 41 to 48 (values 0 to 255)
14
X
X
X
X
X
X
X
X
Terminals 49 to 56 (values 0 to 255)
15
X
X
X
X
X
X
X
X
Terminals 57 to 63 (values 0 to 127)
Содержание IL PB BK DI8 DO4/EF-PAC
Страница 2: ......
Страница 24: ...IL PB BK DI8 DO4 EF PAC 2 14 PHOENIX CONTACT 7725_en_01 ...
Страница 62: ...IL PB BK DI8 DO4 EF PAC 5 2 PHOENIX CONTACT 7725_en_01 ...
Страница 64: ...IL PB BK DI8 DO4 EF PAC 6 2 PHOENIX CONTACT 7725_en_01 ...
Страница 72: ...IL PB BK DI8 DO4 EF PAC A 8 PHOENIX CONTACT 7725_en_01 ...