Appendix
7725_en_01
PHOENIX CONTACT
A-1
A Appendix
A 1
Error codes for PCP communication
Table A-1
06
hex
/02
hex
(Hardware fault)
Meaning
Access to the object failed due to a hardware fault.
Cause
E.g., I/O voltage not present.
Remedy
Remove the hardware fault.
Table A-2
06
hex
/03
hex
(Object access denied)
Meaning
The object has limited access rights.
Cause
It may be a read-only object or it may be password-protected.
Remedy
Check the access rights in the object description.
Table A-3
06
hex
/05
hex
(Object attribute inconsistent)
Meaning
A service parameter was specified with an impermissible value.
Cause
E.g., an incorrect length specification or an impermissible subindex.
Remedy
Check the parameters in the object description and send the service
again with the corrected values.