Diagnostics
7725_en_01
PHOENIX CONTACT
2-11
2.2.2
Error type and error no.
In the controller, error type and error no. are available via status-PDU diagnostics.
Table 2-9
Error type and error no. (also FS/FN flashing codes)
Error type
(FS ON,
FN flashing)
Error no.
(FS OFF,
FN flashing)
Error cause
Error remedy
1
Parameter errors on PROFIBUS
1
A parameter block is faulty.
The number of terminals does not correspond to the
number of parameter blocks or the header byte of the
module parameter is incorrect or the parameter block
is incomplete.
2
Too many data blocks for the
station.
The number of terminals does not correspond to the
number of parameter blocks.
3
The data length of the parameter
block is too short.
Check the number of parameters.
4
The PD PCP module appears
several times in the configuration.
Check the configuration with regard to the number of
PD PCP modules. There must only be one PD PCP
module. (Except for PROFIsafe terminals - these have
two PD PCP modules).
5
The data block length was
exceeded.
Check the number of terminals.
6
A parameter block is not
complete.
Check the structure of the parameters for the
terminals.
7
The number of parameter blocks
is larger than the maximum
number of terminals in the station.
Check the configuration.
8
F-Parameter error,
PROFIsafe-parameter error
Activate Status-PDU diagnostics when
parameterizing the bus coupler in your controller and
determine the exact error location and error cause.
9
iParameter error, PROFIsafe
parameter error
Activate Status-PDU diagnostics when
parameterizing the bus coupler in your controller and
determine the exact error location and error cause.
Содержание IL PB BK DI8 DO4/EF-PAC
Страница 2: ......
Страница 24: ...IL PB BK DI8 DO4 EF PAC 2 14 PHOENIX CONTACT 7725_en_01 ...
Страница 62: ...IL PB BK DI8 DO4 EF PAC 5 2 PHOENIX CONTACT 7725_en_01 ...
Страница 64: ...IL PB BK DI8 DO4 EF PAC 6 2 PHOENIX CONTACT 7725_en_01 ...
Страница 72: ...IL PB BK DI8 DO4 EF PAC A 8 PHOENIX CONTACT 7725_en_01 ...