For group 3, the Switch will report (1) ON/OFF status of Relay2 (2) Instant
Power Consumption (Watt) of Relay2 (3) Accumulated Power Consumption
(KWh) of Relay2 to Z-Wave Controller.
2-1 Auto report to Grouping 1 ~3(Maximum Node 1)
2-1-1 On/Off Event Report
When “on” or “off” state has been changed, it will send Binary Switch Report
to the nodes of Group1~3.
Binary Switch Report
ON:
[Command Class Switch Binary, Switch Binary Report, Value
=255(0xFF)]
OFF:
[Command Class Switch Binary, Switch Binary Report, Value
=0(0x00)]
2-1-2 Instant Power Consumption vary over 5% report
When the power consumption of load vary over 5%, it will send Meter report
to the nodes of Group
Meter Report Command:
[Command Class Meter
,
Meter Report
,
Rate Type = 0x01
,
Meter Type =
0x01
,
Precision = 1
,
Scale = 0x02
,
Size = 4
,
Meter Value(W) ]
2-1-3 overload alarm report command
When PAN04 detect the overload, it will send Alarm Report to the correspond
Group
。
The content of Alarm Report
Alarm report command:
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08,
Alarm Level = 0xFF]
2-2 Response to Meter Get Command
The Switch will report its (1) instant Power Consumption (Watt) or (2)
accumulated power consumption(KWH) or (3)
AC load Voltage (V) or (4)
AC
load current ( I ) (5)
load power factor (PF) to Z-Wave Controller after
receive the Meter Get Command from Z-Wave Controller.
2-2-1 Instant Power Consumption (Watt) of Switch
When receiving Meter Get Command, it will report Meter Report Command to
the node asked.
Meter Get Command:
[Command Class Meter, Meter Get, Scale =0x02(W)]
Meter Report Command:
[Command Class Meter
,
Meter Report
,
Rate Type = 0x01
,
Meter Type
=0x01
,
Precision = 1
,
Scale = 0x02
,
Size = 4
,
Meter Value(W) ]