14
SETTING OF CHAMBER TEMPERATURE
Set the temperature of refrigerator or freezer according to the usage condition. This unit keeps the
storage items for long period with adequate chamber temperature.
Refrigerator
Freezer
Setting range
between 2
o
C and 14
o
C
between -35
o
C and -15
o
C
Initial setting (at factory)
5
o
C
-30
o
C
Example: Changing the refrigerator temperature to 4
o
C from 5
o
C and freezer temperature to -25
o
C from
-30
o
C.
•
Following shows an example. Change the setting as necessary.
Operation
Key operated
Display after operation
1
Connect the power supply cord to
the outlet and turn on the power
switch. (only when start-up)
-----
The temperature display indicator
for refrigerator is lit and the current
refrigerator temperature is displayed
with blink.
2 Press the set key.
SET
The current setting of refrigerator
(005) is displayed and the second
figure 0 blinks.
3
Press the scroll key.
The first figure 5 blinks.
Change 5 to 4 by pressing the up
arrow key.
The display changes to 004 from
005.
4 Press the set key.
SET
The setting is memorized and the
current refrigerator temperature is
displayed with blink.
5
Press the temperature display
changeover key to display the
freezer temperature.
The temperature display indicator
for freezer is lit and the current
freezer temperature is displayed
with blink.
6 Press the set key.
SET
The current setting of freeze (-30) is
displayed and the second figure 3
blinks.
7
Change 3 to 2 by pressing the up
arrow key.
The display changes to-20 from -30.
Press the scroll key.
The first figure 0 blinks.
Change 0 to 5 by pressing the up
arrow key.
The display changes to-25 from -20.
8 Press the set key.
SET
The setting is memorized and the
current freezer temperature is
displayed with blink.
The setting mode returns to the temperature display mode automatically when 90 seconds has passed
without any key operation (auto-return function). In this case, the setting is not accepted.
CAUTION
It is recommended to install a temperature recorder (optional component) when items that need severe
temperature control is stored. The maximum and minimum chamber temperature can be checked.
REF.
FREEZ.