background image

Switched Units: Default functions of the control switches

Switch Position

POT

Notes

Factory Default 
Configuration. 
Run Forward or Reverse  
with speed controlled from 
the Local POT.

Run Reverse

STOP

Run Forward

Sets the output frequency

NOTE

Other functions are possible, please refer to the online documentation for additional information.

Using the Control Terminals

Connection Example

Factory Default Functions

No.

Description

DI1

0/1

Open : Stop

Closed : Run

DI2

3

/

4

Open : Forward Rotation

Closed : Reverse Rotation

DI3

Analog Speed Reference / 
Preset Speed

Open : Speed Reference set by Analog Speed Reference 
Closed : Speed Reference set by Preset Speed 1 (P-20)

AI1

Analog Speed Reference 
Input

Sets the Speed Reference

NOTE

 For Switched units, the internal pot is selected by default in P-16. 

For Non-switched units, an external pot or 0 - 10 V reference may be connected. Other 
signal types may also be used, set P-16 to the correct format.

NOTE

Additional functions are possible, refer to the online documentation for further information.

Motor Thermistor Connection

Where a motor thermistor is to be used, it should be connected as follows:

Control Terminal Strip

Additional Information

Compatible Thermistor: PTC Type, 2.5kΩ trip level.

ƒ

Use a setting of P-15 that has Input 3 function as External Trip, 
e.g. P-15 = 3. Refer to online documentation for further details.

ƒ

Set P-47 = “

SWFWK

"

5   CHECK

+24 

VDC

DI1

DI2

DI3 
AI2

+10 

VDC

DI4 
AI1

0V

A0

0V

RL1

RL2

Nr.

Purpose

Function

1

+24 VDC 100 mA Output

24 VDC Output

2

DI1 Digital Input 1

Function defined by  
P-12 & P-15. 
See below for futher info

3

DI2 Digital Input 2

4

DI3 Digital Input 3/AI2 Analog Input 2

5

+10 VDC 10 mA Output

10 VDC Output for external potentiometer

6

DI4 Digital Input 4/AI1 Analog Input 1

Function defined in P-12 & P-15. Signal format selected in P-16

7

0 VDC Common

8

AO Analog Output/Digital Output

Funktion selected in P-25. See Parameter list

9

0 VDC Common

10

RL1 Output Relay

Function defined in P-18. See Parameter list

11

RL2 Output Relay

Содержание VDI-037-3E3-IP66

Страница 1: ...e l e c t r o n i c AC Converter VersiDrive i E3S IP66ODS Quick Start Manual Quality is our drive...

Страница 2: ...ersiDrive must be mounted in a vertical position only Installation should be on a suitable at ame resistant surface Do not mount ammable material close to the drive Refer to Technical Data and ensure...

Страница 3: ...ve Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient...

Страница 4: ...egulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9 1...

Страница 5: ...he line side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand volt...

Страница 6: ...ed set P 16 to the correct format NOTE Additional functions are possible refer to the online documentation for further information Motor Thermistor Connection Where a motor thermistor is to be used it...

Страница 7: ...econd The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters 67R3 3 3 3 3 Press and hold the Navigate key 2 seco...

Страница 8: ...al Keypad Control 3 Modbus Network Control 4 Modbus Network Control 5 PI Control 6 PI Analog Summation Control 7 CAN Control 8 CAN Control 9 Slave Mode NOTE When P 12 1 2 3 4 7 8 or 9 an enable signal...

Страница 9: ...ly Closed operation is supported depending on Index 2 setting The drive will remain in Fire Mode until disabled or powered off P 31 Keypad Start Mode Select 0 7 1 0 Minimum Speed Keypad Start 1 Previo...

Страница 10: ...owing procedure can be used 1 The motor must be correctly connected to the drive and safe to operate before using this procedure 2 Ensure the motor rated voltage P 07 and current P 08 have been correc...

Страница 11: ...Maximum Cable Size Output Current Recommended Brake Resistance Non UL UL mm AWG A 110 115 10 V 1 Phase Input 3 Phase Output 1 0 37 0 5 8 5 16 15 8 8 7 0 2 0 75 1 12 5 16 15 8 8 10 5 100 200 240 10 V 1...

Страница 12: ...13 DC bus ripple too high 3 266 14 Input phase loss trip K 2 15 Output Over Current WK OW 16 Faulty thermistor on heatsink G W 17 Internal memory fault IO 18 4 20mA Signal Lost G W 19 Internal memory...

Страница 13: ...Phone 49 0 9189 4147 0 Fax 49 0 9189 4147 47 eMail mail peter electronic com PETER electronic GmbH Co KG Bruck cker 9 D 92348 Berg www peter electronic com...

Отзывы: