Information for UL Compliance

VersiDrive E3S is designed to meet the UL requirements. For an up to date list of UL compliant products, please refer to UL 
listing NMMS.E226333. In order to ensure full compliance, the following must be fully observed.

Input Power Supply Requirements

Supply Voltage

200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum.

380 – 480 Volts for 400 Volt rated units, + / - 10% variation allowed, Maximum 500 Volts RMS.

Frequency

50 – 60Hz + / - 5% Variation

Short Circuit 
Capacity

All drives are suitable for use on a circuit capable of delivering not more than 100kA maximum short-
circuit Amperes symmetrical with the specified maximum supply voltage when protected by Class J fuses.

Mechanical Installation Requirements

All VersiDrive E3S units are intended for installation within controlled environments which meet the condition limits shown in 
the Environment section of this Quick Start Guide.

The drive can be operated within an ambient temperature range as stated in the Environment section of this Quick Start Guide.

For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible.

Electrical Installation Requirements

Incoming power supply connection must be according to the Install the Wiring section of this Quick Start Guide.

Suitable power and motor cables should be selected according to the data shown in Rating Tables section of this Quick 
Start Guide and the National Electrical Code or other applicable local codes.

Motor Cable

75°C Copper must be used.

Power cable connections and tightening torques are shown in the Mechanical Dimensions section of this Quick Start Guide.

Integral Solid Sate short circuit protection does not provide branch circuit protection. Branch circuit protection must be 
provided in accordance with the national electrical code and any additional local codes. Ratings are shown in the Rating 
Tables section of this Quick Start Guide.

For Canadian installations transient surge suppression must be installed on the line side of this equipment and shall be rated 
480Volt (phase to ground), 480 Volt (phase to phase), suitable for over voltage category iii and shall provide protection for 
a rated impulse withstand voltage peak of 2.5kV.

UL Listed ring terminals / lugs must be used for all bus bar and grounding connections.

General Requirements

VersiDrive E3S provides motor overload protection, set at 150% of full load, in accordance with the National Electrical Code 
(US).
Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-60 = 1.
Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information 
shown in the Motor Thermistor Connection section of the Quick Start Guide.

UL rated ingress protection (“Type” ) is only met when cables are installed using a UL recognized bushing or fitting for a 
flexible conduit system which meets the required level of protection (“Type”).

For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC.

Not intended for installation using rigid conduit system.

WARNING:

 The opening of the branch-circuit protective device may be an indication that a fault has been interrupted. To reduce 

the risk of fire or electric shock, current-carrying parts and other components of the controller should be examined and replaced if 
damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.

Control Terminal Wiring

ƒ

All analog signal cables should be suitably shielded. 
Twisted pair cables are recommended.

ƒ

Power and Control Signal cables should be routed 
separately where possible, and must not be routed parallel 
to each other.

ƒ

Signal levels of different voltages e.g. 24 Volt DC and 110 
Volt AC, should not be routed in the same cable.

ƒ

Maximum control terminal tightening torque is 0.5Nm.

ƒ

Control Cable entry conductor size: 0.05 – 2.5mm2 /  
30 – 12 AWG.

Control Terminal Connections

Switched Units:

 May use the built in control switch and 

potentiometer, or external control signals connected to the 
control terminals.

Non-Switched Units:

 Require external control signals to 

be connected to the control terminals.

Содержание VDI-037-3E3-IP66

Страница 1: ...e l e c t r o n i c AC Converter VersiDrive i E3S IP66ODS Quick Start Manual Quality is our drive...

Страница 2: ...ersiDrive must be mounted in a vertical position only Installation should be on a suitable at ame resistant surface Do not mount ammable material close to the drive Refer to Technical Data and ensure...

Страница 3: ...ve Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient...

Страница 4: ...egulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9 1...

Страница 5: ...he line side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand volt...

Страница 6: ...ed set P 16 to the correct format NOTE Additional functions are possible refer to the online documentation for further information Motor Thermistor Connection Where a motor thermistor is to be used it...

Страница 7: ...econd The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters 67R3 3 3 3 3 Press and hold the Navigate key 2 seco...

Страница 8: ...al Keypad Control 3 Modbus Network Control 4 Modbus Network Control 5 PI Control 6 PI Analog Summation Control 7 CAN Control 8 CAN Control 9 Slave Mode NOTE When P 12 1 2 3 4 7 8 or 9 an enable signal...

Страница 9: ...ly Closed operation is supported depending on Index 2 setting The drive will remain in Fire Mode until disabled or powered off P 31 Keypad Start Mode Select 0 7 1 0 Minimum Speed Keypad Start 1 Previo...

Страница 10: ...owing procedure can be used 1 The motor must be correctly connected to the drive and safe to operate before using this procedure 2 Ensure the motor rated voltage P 07 and current P 08 have been correc...

Страница 11: ...Maximum Cable Size Output Current Recommended Brake Resistance Non UL UL mm AWG A 110 115 10 V 1 Phase Input 3 Phase Output 1 0 37 0 5 8 5 16 15 8 8 7 0 2 0 75 1 12 5 16 15 8 8 10 5 100 200 240 10 V 1...

Страница 12: ...13 DC bus ripple too high 3 266 14 Input phase loss trip K 2 15 Output Over Current WK OW 16 Faulty thermistor on heatsink G W 17 Internal memory fault IO 18 4 20mA Signal Lost G W 19 Internal memory...

Страница 13: ...Phone 49 0 9189 4147 0 Fax 49 0 9189 4147 47 eMail mail peter electronic com PETER electronic GmbH Co KG Bruck cker 9 D 92348 Berg www peter electronic com...

Отзывы: