Par.
Description
Min
Max
Default
Units
P-23
Preset Frequency / Speed 4
-P-01
P-01
P-09
Hz/RPM
P-24
2nd Ramp Time (Fast Stop)
0.00
600.0
0.00
s
P-25
Analog Output Function Select
0
11
8
-
Digital Output Mode. Logic 1 = +24V DC
Analog Output Mode
0: Drive Enabled (Running)
1: Drive Healthy
2: At Target Frequency (Speed)
3: Drive Tripped
4: Output Frequency >= Limit
5: Output Current >= Limit
6: Output Frequency < Limit
7: Output Current < Limit
8: Output Frequency (Motor Speed)
9: Output (Motor) Current
10: Output Power
11: Load Current
P-30
Start/ Restart/ Fire Mode Configuration
Index 1: Start Mode / Auto Restart
N/A
N/A
Edge-r
-
(GJHU
: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a power
on or reset to start the drive.
$XWR
: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed.
$XWR
To
$XWR
: Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals.
Index 2: Fire Mode Input Logic
0
1
0
-
0: Normally Closed (NC) input.
Fire Mode active if input is open.
1: Normally Open (NO) input.
Fire Mode active if input is closed.
Index 3: Fire Mode Input Latch
0
1
0
-
0: Latched input.
The drive will remain in Fire Mode, only as long the fire mode input signal remains
(Normally Open or Normally Closed operation is supported depending on Index 2 setting).
1: Momentary input.
Fire Mode is activated by a momentary signal on the input. Normally Open or Normally Closed
operation is supported depending on Index 2 setting. The drive will remain in Fire Mode until disabled or powered off.
P-31
Keypad Start Mode Select
0
7
1
-
0: Minimum Speed, Keypad Start
1: Previous Speed, Keypad Start
2: Minimum Speed, Terminal Enable
3: Previous Speed, Terminal Enable
4: Current Speed, Keypad Start
5: Preset Speed 4, Keypad Start
6: Current Speed, Terminal Start
7: Preset Speed 4, Terminal Start
P-32
Starting Boost Frequency
0
P-09
P-09
Hz
Sets the frequency used during the starting boost phase of operation refer to section 6.4 for further information.
P-33
Boost Period Duration
0
150
5
s
Time for which the start-up boost period is applied. During this period, the output frequency is set to P-32 and the voltage increases
linearly from P-11 to P-07. Setting P-33 to zero disables boost. See section 6.4 for additional information.
P-34
Brake Chopper Enable (Not Size 1)
0
4
0
-
0: Disabled
1: Enabled With Software Protection
2: Enabled Without Software Protection
3: Enabled With Software Protection
4: Enabled Without Software Protection
P-38
Parameter Access Lock
0
1
0
-
0: Unlocked
1: Locked
P-39
Analog Input 1 Offset
-500.0
500.0
0.0
%
P-40
Index 1: Display Scaling Factor
0.000
16.000
0.000
-
Index 2: Display Scaling Source
0
3
0
-
P-41
PI Controller Proportional Gain
0.0
30.0
1.0
-
P-42
PI Controller Integral Time
0.0
30.0
1.0
s
P-43
PI Controller Operating Mode
0
3
0
-
0: Direct Operation
1: Inverse Operation
2: Direct Operation, Wake at Full Speed
3: Reverse Operation, Wake at Full Speed
P-44
PI Reference (Setpoint) Source Select
0
1
0
-
0: Digital Preset Setpoint
1: Analog Input 1 Setpoint
P-45
PI Digital Setpoint
0.0
100.0
0.0
%