Technical Data

Environment

Operational ambient temperature range  
Enclosed Drives: 

-20 ... 40°C (frost and condensation free)

Storage ambient temperature range:   -40 … 60°C
Maximum altitude:  

2000m. Derate above 1000m: 1% / 100m

Maximum humidity: 

95%, non-condensing

Rating Tables

Frame 

Size

kW

HP

Input 

Current

Fuse/MCB      

(Typ B)

Maximum Cable 

Size

Output 

Current

Recommended 

Brake Resistance

Non UL

UL

mm

AWG

A

Ω

110 - 115 (+ / - 10%) V 1 Phase Input, 3 Phase Output

1

0,37

0,5

8,5

16

15

8

8

7,0

-

2

0,75

1

12,5

16

15

8

8

10,5

100

200 - 240 (+ / - 10%) V 1 Phase Input, 3 Phase Output

1

0,37

0,5

6,0

10

10

8

8

4,3

-

1

0,75

1

9,3

16

15

8

8

7,0

-

1

1,1

1,5

14,0

20

20

8

8

10,5

100

NOTE

 Cable sizes shown are the maximum possible that may be connected to the drive. Cables should be selected 

according to local wiring codes or regulations at the point of installation.

Содержание VDI-037-3E3-IP66

Страница 1: ...e l e c t r o n i c AC Converter VersiDrive i E3S IP66ODS Quick Start Manual Quality is our drive...

Страница 2: ...ersiDrive must be mounted in a vertical position only Installation should be on a suitable at ame resistant surface Do not mount ammable material close to the drive Refer to Technical Data and ensure...

Страница 3: ...ve Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient...

Страница 4: ...egulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9 1...

Страница 5: ...he line side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand volt...

Страница 6: ...ed set P 16 to the correct format NOTE Additional functions are possible refer to the online documentation for further information Motor Thermistor Connection Where a motor thermistor is to be used it...

Страница 7: ...econd The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters 67R3 3 3 3 3 Press and hold the Navigate key 2 seco...

Страница 8: ...al Keypad Control 3 Modbus Network Control 4 Modbus Network Control 5 PI Control 6 PI Analog Summation Control 7 CAN Control 8 CAN Control 9 Slave Mode NOTE When P 12 1 2 3 4 7 8 or 9 an enable signal...

Страница 9: ...ly Closed operation is supported depending on Index 2 setting The drive will remain in Fire Mode until disabled or powered off P 31 Keypad Start Mode Select 0 7 1 0 Minimum Speed Keypad Start 1 Previo...

Страница 10: ...owing procedure can be used 1 The motor must be correctly connected to the drive and safe to operate before using this procedure 2 Ensure the motor rated voltage P 07 and current P 08 have been correc...

Страница 11: ...Maximum Cable Size Output Current Recommended Brake Resistance Non UL UL mm AWG A 110 115 10 V 1 Phase Input 3 Phase Output 1 0 37 0 5 8 5 16 15 8 8 7 0 2 0 75 1 12 5 16 15 8 8 10 5 100 200 240 10 V 1...

Страница 12: ...13 DC bus ripple too high 3 266 14 Input phase loss trip K 2 15 Output Over Current WK OW 16 Faulty thermistor on heatsink G W 17 Internal memory fault IO 18 4 20mA Signal Lost G W 19 Internal memory...

Страница 13: ...Phone 49 0 9189 4147 0 Fax 49 0 9189 4147 47 eMail mail peter electronic com PETER electronic GmbH Co KG Bruck cker 9 D 92348 Berg www peter electronic com...

Отзывы: