VisuNet GXP
Mechanical Installation
3.3.5
Grounding the Housing to the Pedestal
When installing the VisuNet GXP system, always ensure that all components are properly
grounded, including housing and mounting parts (e.g., pedestal and wall bracket) with a cable
diameter of at least 4 mm
2
in accordance with IEC 60079-14.
When the AG-XX00 housing option is selected, the VisuNet GXP is shipped with the following
PE connections:
•
PE wire from the DPU PE stud to the AG-XX00 housing PE stud
•
PE wire from the PSU PE stud to the AG-XX00 housing PE stud
If you replace the DPU or PSU, reestablish the PE connection in the same configuration.
Tighten the PE hardware to 7.5 Nm.
Figure 3.8
Factory-assembled ground connections to the housing
Warning!
Connection to the PE studs
Connection to the PE studs is mandatory.
Warning!
Operator responsibility to verify grounding path
Check the grounding path after completing system installation.
Warning!
Risk of personal injury and equipment damage
Pinched PE wire
Ensure that the PE wire does not become pinched between the pedestal and housing.
Danger!
Explosion hazard from wrong or missing grounding
Wrong or missing grounding can cause sparks. This can ignite the surrounding potentially
explosive atmosphere.
•
Ground the device. Observe the grounding requirements.
•
Ensure that external ground connections exist, are in good condition, and are not
damaged or corroded.
VisuNet GXP
System Installation