Series Operation
Devices of the same type can be connected in series for higher output voltages.
It is possible to connect as many units in series as needed, providing the sum of the output
voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc must be installed
with a protection against touching.
Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output
terminals.
Restrictions
•
Keep an installation clearance of 15mm (left / right) between two power supplies
and avoid installing the power supplies on top of each other.
•
Do not use power supplies in series in mounting orientations other than the standard
mounting orientation (terminals on the bottom of the unit).
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using
multiple power supplies.