20
21
-1
1
30
Power Supply PS1000-A6-24.20
Safety Features
20
Safety Features
Class of protection
I
PE (Protective Earth) connection required
According to IEC 61140
Isolation resistance
>500MOhm
At delivered condition between input and output,
measured with 500Vdc
>500MOhm
At delivered condition between input and PE,
measured with 500Vdc
>500MOhm
At delivered condition between output and PE,
measured with 500Vdc
>500MOhm
At delivered condition between output
and DC-OK contacts, measured with 500Vdc
PE resistance
<0.1Ohm
Resistance between PE terminal and the housing
in the area of the DIN rail mounting bracket.
Touch current (leakage current) typ. 0.12mA / 0.31mA
At 100Vac, 50Hz, TN-, TT-mains / IT-mains
typ. 0.18mA / 0.45mA
At 120Vac, 60Hz, TN-, TT-mains / IT-mains
typ. 0.3mA / 0.76mA
At 230Vac, 50Hz, TN-, TT-mains / IT-mains
max. 0.16mA / 0.38mA At 110Vac, 50Hz, TN-, TT-mains / IT-mains
max. 0.23mA / 0.55mA At 132Vac, 60Hz, TN-, TT-mains / IT-mains
max. 0.39mA / 0.94mA At 264Vac, 50Hz, TN-, TT-mains / IT-mains