Power Supply PS1000-A6-24.20
Input Inrush Current
20
21
-1
1
13
7
Input Inrush Current
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds
after switch-on.
Figure 7.1
Typical turn-on behavior at nominal load and 25°C ambient
AC 100V
AC 120V
AC 230V
Inrush current
Max.
15A
peak
12A
peak
5.5A
peak
Temperature independent
Typ.
12A
peak
10A
peak
4.5A
peak
Temperature independent
Inrush energy
Max.
1A²s
1A²s
1A²s
Temperature independent
Содержание PS1000-A6-24.20
Страница 1: ...ISO9001 PS1000 A6 24 20 Power Supply Technical Information...
Страница 4: ...Power Supply PS1000 A6 24 20 Contents 4 2021 11...
Страница 16: ...2021 11 16 Power Supply PS1000 A6 24 20 Output Figure 8 4 Output voltage in Parallel Use mode typ...
Страница 24: ...2021 11 24 Power Supply PS1000 A6 24 20 Functional Diagram 15 Functional Diagram Figure 15 1 Functional diagram...
Страница 28: ...2021 11 28 Power Supply PS1000 A6 24 20 Environment Figure 18 2 Output current vs altitude...