Power Supply PS1000-A6-24.20
Front Side and User Elements
20
21
-1
1
25
16
Front Side and User Elements
Figure 16.1 Front side
1 Output Terminals
Screw terminals, two identical (+) poles
and three identical (-) poles
(+) Positive output
(–) Negative (return) output
2 Output Voltage Potentiometer
Open the flap to adjust the output voltage.
Factory set: 24.1V
3 DC-OK LED
(green)
On, when the output voltage is >90%
of the adjusted output voltage.
4 Parallel Use/Single Use Link
Link the two terminal poles when power
supplies are connected in parallel. In order
to achieve a sharing of the load current
between the individual power supplies,
the
Parallel Use
regulates the output voltage
in such a manner that the voltage at no load
is approx. 4% higher than at nominal load.
See also chapter 26.4.
5 DC-OK Relay Contact
Push-in terminals
The DC-OK relay contact is synchronized with
the DC-OK LED. See chapter 10 for details.
6 Input Terminals
Screw terminals
N, L Line input
PE (Protective Earth) input
OUTPUT DC 24V 20A
DC OK
24 - 28V
PS1000-A6-24.20
Part No. 70103523
Power Supply
Link for
Parallel use
13
14
DC OK
N L
AC 100-240V
INPUT
6
4
5
3
2
1
Содержание PS1000-A6-24.20
Страница 1: ...ISO9001 PS1000 A6 24 20 Power Supply Technical Information...
Страница 4: ...Power Supply PS1000 A6 24 20 Contents 4 2021 11...
Страница 16: ...2021 11 16 Power Supply PS1000 A6 24 20 Output Figure 8 4 Output voltage in Parallel Use mode typ...
Страница 24: ...2021 11 24 Power Supply PS1000 A6 24 20 Functional Diagram 15 Functional Diagram Figure 15 1 Functional diagram...
Страница 28: ...2021 11 28 Power Supply PS1000 A6 24 20 Environment Figure 18 2 Output current vs altitude...