Power Supply PS1000-A6-24.20
EMC
17
EMC
The EMC behavior of the device is designed for applications in industrial environment
as well as in residential, commercial and light industry environments. The output is allowed
to be grounded or floating.
Without additional measures to reduce the conducted emissions on the output (e.g. by using
a filter), the device is not suited to supply a local DC power network in residential, commercial
and light-industrial environments. No restrictions apply for local DC power networks
in industrial environments.
EMC Immunity
According to generic standards: EN 61000-6-1, EN 61000-6-2, EN 61000-6-3
and EN 61000-6-4
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3
80MHz-2.7GHz
20V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L
→
N
L
→
PE, N
→
PE
2kV
2kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5
+
→
–
+ / –
→
PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on DC-OK EN 61000-4-5
Signal lines
→
PE
1kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
20V
Criterion A
Mains voltage dips
EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11 0% of 200Vac (=0V)
5000ms
Criterion C
Powerful transients
VDE 0160
Over entire load range
750V, 0.3ms
Criterion A
Criterion A
The device shows normal operation behavior within the defined limits.
Criterion C
Temporary loss of function is possible. Power supply may shut-down and restarts by itself.
No damage or hazards for the power supply will occur.
EMC Emission
Conducted emission input lines
EN 55011, EN 55032, FCC Part 15,
CISPR 11, CISPR 32
Class B
Radiated emission
EN 55011, EN 55032
Class B
Harmonic input current (PFC)
EN 61000-3-2
Fulfilled for Class A equipment
Fulfilled for Class C equipment
in the load range from 8 to 24A
Voltage fluctuations, flicker
EN 61000-3-3
Fulfilled, tested with constant current
loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired
operation.
Switching Frequencies
PFC converter
110kHz
Fixed frequency
Main converter
84kHz to 140kHz
Output load dependent
Auxiliary converter
60kHz
Fixed frequency
Содержание PS1000-A6-24.20
Страница 1: ...ISO9001 PS1000 A6 24 20 Power Supply Technical Information...
Страница 4: ...Power Supply PS1000 A6 24 20 Contents 4 2021 11...
Страница 16: ...2021 11 16 Power Supply PS1000 A6 24 20 Output Figure 8 4 Output voltage in Parallel Use mode typ...
Страница 24: ...2021 11 24 Power Supply PS1000 A6 24 20 Functional Diagram 15 Functional Diagram Figure 15 1 Functional diagram...
Страница 28: ...2021 11 28 Power Supply PS1000 A6 24 20 Environment Figure 18 2 Output current vs altitude...