Fieldbus Valve Coupler FD0-VC-Ex4.FF
Error detection and problem solutions
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
P
a
rt
N
o
.:
1
082
27
, D
a
te
o
f i
ssue
27
.0
3.2
006
7.4
Function block DO
Diagnosis messages
Miscellaneous
Problem
Elimination of error
Parameter
Message
Cause
Elimination
BLOCK_ERR Block Configuration
Error
The parameter "CHANNEL"
has not been assigned a valid
value (1 ... 4).
Assign valid value (see section
6.3).
The function block was not
assigned a schedule.
Include the function block in a
function block application and
load this in the device.
The target mode of the block is
"RCas" and "SHED_OPT" is at
"undefined".
Assign valid value, e. g. "Normal
Schedule - Normal Return".
Input Failure
The status of PV_D is "bad".
• Check the value fed back by the
transducer block.
• Check diagnosis message of
transducer block.
Output Failure
There is an error in the trans-
ducer block which affects the
output.
Check diagnosis message of
transducer block (section 7.3).
Simulate
Simulation for this block is acti-
vated.
See section 5.4.2 and appendix
B.
Local Override
The reference value has been
overwritten by the safety value
via the bus due to as missing
reference value specification.
• Check communication.
• Check device which specifies
the reference value.
Out of Service
The block is in "Out of Service"
mode.
• Select suitable target mode.
• Check block configuration error.
Problem
Cause
Elimination
Cross
reference
The function block does not leave
the "Out of Service" mode
There is a block configura-
tion error which is signalled
in "BLOCK_ERR".
See "Diagnosis
messages".
See "Diagnosis
messages".
The resource block is in
"Out of Service" mode.
Set resource block
into "AUTO" mode.
The value of OUT_D is displayed in
READBACK_D instead of the value
fed back by the transducer block
The option "readback sup-
ported" in parameter
"FEATURES_SEL" of the
resource block is not set.
Set option.
The value of OUT_D is not trans-
ferred to the transducer block
Simulation is ON.
Switch OFF simula-
tion.
Simulation cannot be activated
The simulation switch is not
switched ON.
Check in resource
block whether the
simulation switch is
ON; switch ON, if
necessary.
Parameters cannot be written
Write protection activated.
Deactivate write
protection.
See section
5.4.2 and
appendix C.