21
Fieldbus Valve Coupler FD0-VC-Ex4.FF
Installation
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
P
a
rt
N
o
.:
1
082
27
, D
a
te
o
f i
ssue
27
.0
3.2
006
5.4.3
Connection of auxiliary valves and final position feedback contacts
The following illustration shows the location and designation of the terminals for valve connection and PFCs.
Figure 5.4: Location and designation of the connector terminals for the valve connection incl. final position feedback contacts
Terminal assignment
As described in section 4.2.4, the PFCs are used in the 2:1 procedure. For the connection of sensors or
mechanical contacts the possible connections are shown in figure 5.5; terminals 3 and 4 are given as
examples.
Terminal
Signal
Explanation
1
Valve 1 +
Output, trigger signal for valve 1
2
Valve 1 –
3
PFC 1A +, PFC 1B –
2 inputs, signals of 2 PFCs from valve 1, transfer by 2:1 procedure
4
PFC 1A –, PFC 1B +
5
Valve 2 +
Output, trigger signal for valve 2
6
Valve 2 –
7
PFC 2A +, PFC 2B –
2 inputs, signals of 2 PFCs from valve 2, transfer by 2:1 procedure
8
PFC 2A –, PFC 2B +
9
Valve 3 +
Output, trigger signal for valve 3
10
Valve 3 –
11
PFC 3A +, PFC 3B –
2 inputs, signals of 2 PFCs from valve 3, transfer by 2:1 procedure
12
PFC 3A –, PFC 3B +
13
Valve 4 +
Output, trigger signal for valve 4
14
Valve 4 –
15
PFC 4A +, PFC 4B –
2 inputs, signals of 2 PFCs from valve 4, transfer by 2:1 procedure
16
PFC 4A –, PFC 4B +
PA
Equipotential bon-
ding
Connection for equipotential bonding and/or connection for the
screen between the valve coupler and valve and PFC. Preferably no
screened cable should be used here
Connector terminals for the
valves and final position sensors