Fieldbus Valve Coupler FD0-VC-Ex4.FF
Installation
20
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
P
a
rt
N
o
.: 1
082
27
, D
a
te
o
f i
ssue
27
.0
3.2
006
5.4.2
Connection of fieldbus and DIP switch settings
The following illustration shows the location and designation of the connector terminals for the bus connec-
tion and the DIP swithes to switch-on and off simulation and write protection.
Figure 5.3: Location and designation of the connector terminals for bus connection
Terminal assignment
DIP switch settings
Switch 1:
Simulation ON/OFF
With activated simulation (simulation setting ON) the valve position transferred from the
transducer block to the function block can be set by the control system independent from
the actual valve position.
Switch 2:
Hardware write protection ON/OFF
Parameterisation of the device via the bus is no longer possible when write protection is
activated (setting ON).
Switch 3 ... 8:
not used
Terminal
Signal
Explanation
+
FF-H1 +
Fieldbus FF bus cable +
S
Screen
Screen of bus cable
–
FF-H1 –
Fieldbus FF bus cable –
Connector terminals for
F
OUNDATION
fieldbus
Hardware write protection
not used
ON: active
OFF: not active (default setting)
ON
OFF
3
4 5
6 7
8
1 2
Simulation