Fieldbus Valve Coupler FD0-VC-Ex4.FF
Resource block
54
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: G49 621 776-0 • USA +1 330 4253555 • Sin65 67799091 • Internet http://www.pepperl-fuchs.com
P
a
rt
N
o
.:
1
082
27
, D
a
te
o
f i
ssue
27
.0
3.2
006
C
Resource block
The column "Char." shows which characteristics or conditions are applicable to this parameter. The follow-
ing is applicable here:
•
OOS (Out of Service)
The parameter can be written only if the target mode of the block is "Out of Service".
•
S (Static)
During each writing process to such an identified parameter the parameter ST_REV is increased by one.
•
W (Writeable)
The parameter can be modified by the user.
As all parameters can be read this is not marked especially.
Parameter
Char.
Description
ST_REV
During each writing process to a parameter marked by "S" the parameter
ST_REV is increased by one.
TAG_DESC
W
S
Via this parameter the valve interface can be assigned a tag (measuring point
designation) within the plant and/or process.
STRATEGY
W
S
The strategy field can be used to identify comprising blocks. These data are
not controlled or used by the block.
ALERT_KEY
W
S
Identification number of the plant unit. This information can be used by the con-
trol computer, e.g. to sort alarms. Valid values are 1 ... 65536.
MODE_BLK
W
S
Displays the current, allowed normal mode and the target mode of the block.
The target mode can be set to the values "Auto" or "Out of Service".
BLOCK_ERR
Displays diagnosis messages of the block.
RS_STATE
Current status of device.
TEST_RW
Test parameter. Is used to test the device.
DD_RESOURCE
FF standard parameter. Not used.
MANUFAC_ID
Identification number of the device manufacturer - is used by the control sys-
tem to assign the device description (DD) to the device.
DEV_TYPE
Device type - is used by the control system to assign the device description to
the device.
DEV_REV
Version number of the device - is used by the control system to assign the
device description to the device.
DD_REV
Version number of device description - is used by the control system to assign
the device description to the device.
GRANT_DENY
W
Regulates the access rights between control system and local operator's sta-
tions for some control systems.
HARD_TYPES
Hardware type.
RESTART
W
Allows to carry out a new manual start. Different types of re-starts are possible:
There are
• Restart Resource,
• Restart with defaults (default settings),
• Restart processor.
FEATURES
Displays the options supported by the device. These are:
Unicode Strings
Unicode string,
Reports
Alarms,
Fault State
Release of the safe state for the whole device by the
resource block,
Hard Write lock
Hardware read-only feature,
Output Readback
Back-reading of the valve position via the PFCs.
FEATURE_SEL W
S
The options used are selected here.
See FEATURES.
CYCLE_TYPE
Gives the different block implementation methods for this device.