MegaTherm Commercial Pool Heating Boiler

Page 13

If the inlet temperature is LESS THAN 100°F:

With the bypass valve “A” fully open, throttle
(turn down) outlet valve “B” slightly.  Observe
the inlet thermometer for 5 minutes to see where
the inlet temperature stabilizes.  If it remains
under 100°F, throttle outlet valve “B” a little
more.  Repeat as necessary.  If the inlet
temperature rises above 100°F, open outlet valve
“B” slightly until the inlet temperature stabilizes
as close to 100°F as possible (plus or minus 2°F).

If the inlet temperature is MORE THAN

100°F.  

If outlet valve “B” has been throttled

partially closed, open it slightly, wait 5 minutes,
and, if the temperature is not down to 100°F
(plus or minus 2°F) open it some more.  If
bypass valve “B” is fully open and you are still
seeing inlet water temperatures in excess of
100°F, you can adjust bypass valve “A”.
Throttle it (turn down) slightly towards closed,
and wait until the inlet water temperature
stabilizes again.  Repeat as necessary.
When the inlet temperature is stabilized at
100°F, either lock the valve handles, remove
them, or prominently mark them to prevent
tampering or accidental changes to the valve
positions.
If the pool water temperature needs to be raised
more than 10° F to reach a comfortable
swimming temperature, inspect and re-adjust the
valves twice a day to maintain the 100°F inlet
water temperature.

3.

To prevent nuisance high limit tripping, set the
adjustable pump time delay relay to 10 minutes
for all models.  This allows the boiler pump to
circulate water through the heat exchanger after
the burners shut off, recovering all residual heat
in the metal components.

4.

The boiler outlet temperature with the bypass
adjusted as detailed above should be less than
142°F. The normal range will be 10 to 37°F
higher than the inlet temperature.  If it exceeds
142°F, please contact the Service Department at
800-900-9276, extension 5406 for instructions.
Outlet temperatures in excess of 142°F may
cause intermittent high limit tripping.

POOL OPERATING CONTROL ADJUSTMENT:
5.

Adjustable Differential Feature: Remove the
cover from the control box and verify that the
white differential potentiometer is  set at about
2°F (1°C). NOTE: a 2°F

 

differential means that,

if the thermostat is set at 80°F, the heater will
come on at 78°F and go off when the pool
reaches 80°F. The 2°F value is a good starting
point for most installations. This differential may
be adjusted up or down to suit individual
applications.

6.

The operating control temperature setting can be

Figure 14.  Safety Components.

Manual Reset

High Limit

Flow

Switch

Low Water

Cutoff

(Optional)

Figure 15.  Pilot Burners.

Spark ignition

Standing pilot

adjusted incrementally to obtain the desired pool
operating temperature.

3.5 Heater Shut Down

1.

If heater is firing, turn operating control to
lowest value, wait 10 minutes for pump to stop
running, then turn power switch to off.

2.

If heater is not firing, turn power switch to off.

3.6 Spring and Fall Operation

Stand-by Service

Turn the thermostat down to approximately

70°F (21°C). This will prevent the pool and
surrounding ground from becoming chilled and also
permit the pool to be raised to swimming temperature
in a shorter time.

A pool may be maintained at a lower temperature

than 70°F (21°C) with some increased likelihood of
condensation and damage to the unit. Models 500
through 1010 will maintain an inlet temperature of
85°F (29°C) to 90°F (32°C) (if the bypass is properly
adjusted) with a pool temperature of 60°F (16°C).
Models 1200 and 1430 can maintain the above with a
pool temperature of 65°F (18°C). For models 1670

Thermo-

couple

Содержание MegaTherm MT 1010

Страница 1: ...nance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void t...

Страница 2: ...s 9 2 7 Boiler By Pass Piping 9 2 8 Temperature Sensor Placement and Installation 10 2 9 Automatic Chlorinators 10 SECTION 3 Operation 3 1 Controls General 11 3 2 Initial Start Up 11 3 3 Safety Shutof...

Страница 3: ...he procedures MODEL MT POOL REVISION P PUMP U S Q PUMP CAN HEAT EXCHANGER C GLASS LINED COPPER N GLASS LINES CU NI K BRONZE COPPER S BRONZE CU NI VERSION 1 8 TUBE B 10 TUBE I INDOOR E OUTDOOR FUEL N N...

Страница 4: ...ide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223 1 and any local codes that may be applicable Inadequate...

Страница 5: ...al used to maintain clearances and prevent physical damage and separation of joints Avoid terminating boiler vents near air conditioning or air supply fans The fans can pick up exhausted flue products...

Страница 6: ...a summer exhaust fan Close all fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions for the unit Adjust the thermostat so the appliance will operate c...

Страница 7: ...n Outdoor installations are not recommended in areas where the danger of snow blockage exists WARNING Liquefied petroleum gas is heavier than air Therefore the pool heating boiler should not be instal...

Страница 8: ...rwise 2 The 1825 models are supplied with 3 4 HP pump motors All other models are supplied with 1 2 HP pump motors Consult the National Electrical Code or the Canadian Electrical Code regarding branch...

Страница 9: ...ed by the momentary back siphoning of hot water from the heater when the filter pump stops running The pressure relief valve installed in the tapped opening provided in the outlet header see Figure 9...

Страница 10: ...ic Chlorinators A concentration of chlorine in the heater can be very destructive therefore the following rules about the installation and operation of such devices must be followed 1 The chlorinator...

Страница 11: ...he temperature sensor thermistor is located in the filter circulation piping see Section 2 8 3 Boiler Power On Off Auto Switch This provides for constant or automatic pump operation 4 High Limit Contr...

Страница 12: ...cally lit when the operating controls call for heat If the pilot flame fails for any reason the main valve is shut off within one second and the pilot spark ignition is initiated until the pilot flame...

Страница 13: ...etailed above should be less than 142 F The normal range will be 10 to 37 F higher than the inlet temperature If it exceeds 142 F please contact the Service Department at 800 900 9276 extension 5406 f...

Страница 14: ...ic pools or spa pools are usually piped and controlled so that very warm or hot water often with air injection is forced at high velocity into a confined area of a swimming pool or into a small separa...

Страница 15: ...m are unobstructed 6 Check for fouling on the external surfaces of the heat exchanger every six months NOTE after installation and first start up check the heat exchanger for fouling after the followi...

Страница 16: ...itizing chemicals also adds greatly to the mineral content of the pool If the concentration of minerals in the pool is permitted to become too high the minerals will precipitate out of the water and d...

Страница 17: ...at gas valve terminals Check continuity of actuator burned out or shorted coil If open circuit or short is indicated replace coil or operator G Pump does not run G Operate in manual Check power to pum...

Страница 18: ...Rear 10548401 10548402 10548403 10548404 15 Saddle Assembly End Tile 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 2 2 2 2 2 2 2 2 2 16 Lower End Panel 10540701 1054...

Страница 19: ...MegaTherm Commercial Pool Heating Boiler Page 19 Figure 17 Parts Identification...

Страница 20: ...Assembly Copper Tubes 10534701 10534702 10534703 10534704 10534705 10534706 10534707 Cast Iron Tubs Indoor 8 Tube Assembly Copper Tubes 10542901 10542902 10542903 10542904 10542905 10542906 10542907 B...

Страница 21: ...ll Immersion E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E274000 45 Well High Limit E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 46 Valv...

Страница 22: ...W0034400 W0034400 W0034400 W0034400 Standing Pilot LP Pilot Burner Honeywell W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 IID Pilot Nat Pilot Burner Honeywell W2001...

Страница 23: ...0 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 74 Controller Water Temp E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 75 Sensor Water Temp E2103600...

Страница 24: ...d Spa Page 24 Figure 18 Tile Assemblies When ordering tiles Assembly number is for all tiles Part numbers shown for the front of unit are the same for the rear tiles Check dimensions of old tile as sh...

Страница 25: ...MegaTherm Commercial Pool Heating Boiler Page 25 Figure 19 Outdoor Parts 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 20...

Страница 26: ...03 10658104 10658105 10658106 10658107 10658108 10658109 3 Upper Rear Louver shield 10657101 10657102 10657103 10657104 10657105 10657106 10657107 10657108 10657109 4 Upper Rear Panel 10658701 1065870...

Страница 27: ...1 10659302 10659303 10659304 10659305 10659306 10659307 10659308 10659309 20 Pump Cover Assembly 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 Pump Parts Pump Couple...

Страница 28: ...Pentair Water Commercial Pool and Spa Page 28...

Страница 29: ...MegaTherm Commercial Pool Heating Boiler Page 29...

Страница 30: ...Pentair Water Commercial Pool and Spa Page 30...

Страница 31: ...MegaTherm Commercial Pool Heating Boiler Page 31...

Страница 32: ...000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this document to...

Отзывы: