Caution

Black carbon or green soot on a dirty heat
exchanger can, under certain conditions, be
ignited by a random spark or open flame. To
prevent this unlikely occurrence, dampen the
soot deposits with wet brush or fine water
spray before servicing or cleaning the heat
exchanger.

9.

Clean heat exchanger using a wire brush to
remove soot and loose scale from the unit. Clean
fallen debris from bottom of heater. Make sure
burner ports are clear and pilot assembly is free
of debris.

10.

Reassemble in reverse order and be sure the heat
exchanger baffles are replaced.

11.

The gas and electric controls installed on the
heater are engineered for both dependable
operation and long life, but the proper
functioning of these components is necessary for
safe operation of the heater. It is strongly
recommended that the basic items be checked by
a competent serviceman every year and replaced
when necessary. The basic controls are:
a.

Water temperature controls.

b.

Pilot safety system.

c.

Automatic electric gas valve(s)

d.

Flow switch.

12.

Low water cutoffs should be inspected every six
(6) months, when provided.

NOTE:

 The warranty does not cover any

damage caused by lack of required maintenance
or improper operating practices.

13.

Pool Water Chemistry
The mineral content of the pool water increases
every day. This is due to the natural evaporation
which removes only distilled water and leaves the
minerals behind. The regular addition of algicidal
and sanitizing chemicals also adds greatly to the
mineral content of the pool. If the concentration of
minerals in the pool is permitted to become too
high, the minerals will precipitate out of the water
and deposit onto the walls of the pool, in the filter
and in the tubes of the heat exchanger.
For this reason it is very advantageous to drain
the pool regularly (at least every two years). This
precautionary measure will save the cost of
expensive repairs to the finish, filter system and
heater.
Another important safety precaution - always
keep the pH of the pool water between 7.3 and

Figure 16. Main Burner Flame Pattern.

7.7. This will add years to the life of the pool
finish, filter system and heater.
Most algicidal and sanitizing chemicals contain
sodium hypochlorite, while others contain
calcium hypochlorite. Sodium is not a scaling
chemical but calcium is. When using calcium
hypochlorite it is especially important to
frequently check the pH of the pool and to
change the pool water when the dissolved solids
indicate an excessive mineral content.

SECTION 5.
Troubleshooting

For proper service and problem diagnosis of the

heater and heater system, the following tools are
required:

a.

Gas pressure test kit with range from zero to 14
W.C. Either a slack tube manometer or an
accurate gas pressure gauge is acceptable with
proper adapters to connect to the available
fittings in the line and on the gas valve.

b.

Multi-meter with the following ranges:

0 to 500 volts A.C.

0 to 1000 ohms continuity.

0 to 50 millivolts.

c.

Tube cleaning kit consisting of reamer, stainless
steel brush, speed handle and handle extensions.

d.

A pool thermometer with a proper range.

e.

A pressure gauge with proper range.

Содержание MegaTherm MT 1010

Страница 1: ...nance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void t...

Страница 2: ...s 9 2 7 Boiler By Pass Piping 9 2 8 Temperature Sensor Placement and Installation 10 2 9 Automatic Chlorinators 10 SECTION 3 Operation 3 1 Controls General 11 3 2 Initial Start Up 11 3 3 Safety Shutof...

Страница 3: ...he procedures MODEL MT POOL REVISION P PUMP U S Q PUMP CAN HEAT EXCHANGER C GLASS LINED COPPER N GLASS LINES CU NI K BRONZE COPPER S BRONZE CU NI VERSION 1 8 TUBE B 10 TUBE I INDOOR E OUTDOOR FUEL N N...

Страница 4: ...ide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223 1 and any local codes that may be applicable Inadequate...

Страница 5: ...al used to maintain clearances and prevent physical damage and separation of joints Avoid terminating boiler vents near air conditioning or air supply fans The fans can pick up exhausted flue products...

Страница 6: ...a summer exhaust fan Close all fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions for the unit Adjust the thermostat so the appliance will operate c...

Страница 7: ...n Outdoor installations are not recommended in areas where the danger of snow blockage exists WARNING Liquefied petroleum gas is heavier than air Therefore the pool heating boiler should not be instal...

Страница 8: ...rwise 2 The 1825 models are supplied with 3 4 HP pump motors All other models are supplied with 1 2 HP pump motors Consult the National Electrical Code or the Canadian Electrical Code regarding branch...

Страница 9: ...ed by the momentary back siphoning of hot water from the heater when the filter pump stops running The pressure relief valve installed in the tapped opening provided in the outlet header see Figure 9...

Страница 10: ...ic Chlorinators A concentration of chlorine in the heater can be very destructive therefore the following rules about the installation and operation of such devices must be followed 1 The chlorinator...

Страница 11: ...he temperature sensor thermistor is located in the filter circulation piping see Section 2 8 3 Boiler Power On Off Auto Switch This provides for constant or automatic pump operation 4 High Limit Contr...

Страница 12: ...cally lit when the operating controls call for heat If the pilot flame fails for any reason the main valve is shut off within one second and the pilot spark ignition is initiated until the pilot flame...

Страница 13: ...etailed above should be less than 142 F The normal range will be 10 to 37 F higher than the inlet temperature If it exceeds 142 F please contact the Service Department at 800 900 9276 extension 5406 f...

Страница 14: ...ic pools or spa pools are usually piped and controlled so that very warm or hot water often with air injection is forced at high velocity into a confined area of a swimming pool or into a small separa...

Страница 15: ...m are unobstructed 6 Check for fouling on the external surfaces of the heat exchanger every six months NOTE after installation and first start up check the heat exchanger for fouling after the followi...

Страница 16: ...itizing chemicals also adds greatly to the mineral content of the pool If the concentration of minerals in the pool is permitted to become too high the minerals will precipitate out of the water and d...

Страница 17: ...at gas valve terminals Check continuity of actuator burned out or shorted coil If open circuit or short is indicated replace coil or operator G Pump does not run G Operate in manual Check power to pum...

Страница 18: ...Rear 10548401 10548402 10548403 10548404 15 Saddle Assembly End Tile 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 2 2 2 2 2 2 2 2 2 16 Lower End Panel 10540701 1054...

Страница 19: ...MegaTherm Commercial Pool Heating Boiler Page 19 Figure 17 Parts Identification...

Страница 20: ...Assembly Copper Tubes 10534701 10534702 10534703 10534704 10534705 10534706 10534707 Cast Iron Tubs Indoor 8 Tube Assembly Copper Tubes 10542901 10542902 10542903 10542904 10542905 10542906 10542907 B...

Страница 21: ...ll Immersion E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E274000 45 Well High Limit E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 46 Valv...

Страница 22: ...W0034400 W0034400 W0034400 W0034400 Standing Pilot LP Pilot Burner Honeywell W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 IID Pilot Nat Pilot Burner Honeywell W2001...

Страница 23: ...0 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 74 Controller Water Temp E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 75 Sensor Water Temp E2103600...

Страница 24: ...d Spa Page 24 Figure 18 Tile Assemblies When ordering tiles Assembly number is for all tiles Part numbers shown for the front of unit are the same for the rear tiles Check dimensions of old tile as sh...

Страница 25: ...MegaTherm Commercial Pool Heating Boiler Page 25 Figure 19 Outdoor Parts 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 20...

Страница 26: ...03 10658104 10658105 10658106 10658107 10658108 10658109 3 Upper Rear Louver shield 10657101 10657102 10657103 10657104 10657105 10657106 10657107 10657108 10657109 4 Upper Rear Panel 10658701 1065870...

Страница 27: ...1 10659302 10659303 10659304 10659305 10659306 10659307 10659308 10659309 20 Pump Cover Assembly 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 Pump Parts Pump Couple...

Страница 28: ...Pentair Water Commercial Pool and Spa Page 28...

Страница 29: ...MegaTherm Commercial Pool Heating Boiler Page 29...

Страница 30: ...Pentair Water Commercial Pool and Spa Page 30...

Страница 31: ...MegaTherm Commercial Pool Heating Boiler Page 31...

Страница 32: ...000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this document to...

Отзывы: