On a newly constructed pool, be sure to run the

filter pump long enough for a complete “turn-over” of
the pool water before starting heater so that dirt and
residue from construction will have been removed.
The filter may clog rapidly during this period, causing
severe cycling of the heater.

1.

Before placing the heater in operation, be certain
that the heater is filled with water and that all air
is purged from the system. Open all the valves in
the secondary piping.

2.

With the filter pump running, run the heater
pump in manual “CONSTANT PUMP” for
minimum of 10 minutes and listen for the flow
switch to make as the pump is started. Loosen
the pipe plug on the top of the pump scroll
casting to bleed off any air. NOTE: If the system
will be operated in a manner that causes air to be
drawn into the heater and the secondary piping,
an automatic float type air vent should be
permanently installed on top of the pump scroll.

3.

To check the heater firing, proceed as follows:
a.

Turn off the power switch.

b.

Turn off all manual gas valves and wait
five minutes (Figure 13).

c.

Set operating control to the lowest setting.

d.

After placing the manual pilot gas valve in
the open position and resetting all safety
devices (high limit, low water cutoff, etc.),
the pilot(s) can be lit following the
procedure on the heater rating plate.

e.

For standing pilot system, press on pilot
relay knob (see Figure 15), light pilot and
keep relay knob depressed for one minute
then release. Once the pilot is lit, turn
power switch to “AUTO PUMP.”

f.

Wait 5 minutes and turn up operating control
until heater fires (for intermittent ignition
system, the pilot will be ignited automatically).
The main burners should ignite smoothly. Turn
the operating control back to the lowest setting.

NOTE: DO NOT OPERATE HEATER UNTIL
THE FOLLOWING SAFETY CHECKS HAVE
BEEN PERFORMED.

3.3 Safety Shutoff Component Checkout

1.

Once the pilot(s) is lit and has been established
for five minutes, the flame failure response time
should be checked as follows:

Systems 4 and 9

 - (intermittent ignition). With this

system pilots are automatically lit when the operating
controls call for heat. If the pilot flame fails for any
reason, the main valve is shut off within one second

and the pilot spark ignition is initiated until the pilot
flame has been reestablished. This sequence should be
checked by turning off the manual pilot gas valve (see
Figure 14), and, at the same time, monitoring the
audible sparking at the pilot burner and signal
interruption to the main valve.

Caution

Propane gas is heavier than air and sinks to
the ground. Exercise extreme care in lighting
the heater when so equipped.

System 16

 - (electronically supervised standing pilot

system). Extinguish the pilot flame by placing the
manual pilot valve in the closed positions (see
Figure 14), and at the same time, begin recording the
time it takes for the output signal from the electronic
ignition control to be interrupted. The signal
interruption can be detected either with a test light or a
voltmeter. The response time should never exceed one
second.
2.

Hi-Limit Checkout. For spas see Section 3.9. The
manual reset high limit is factory preset to 150°F
(66°C). Confirm this set point on the unit and
adjust if necessary. After running the heater in a
firing mode for 10 minutes, slowly close the
outlet valve “A” to raise the outlet temperature as
indicated on the outlet thermometer. The high
limit should trip within 2°F (1°C) or 3°F (2°C) of
the 150°F (66°C) setpoint and shut off the
burners. If this does not occur, adjust the set
point on the unit to shut off the burners when the
outlet thermometer reads 150°F (66°C). Open the
outlet valve “A” and push the reset button. The
main burners should reignite.

3.

Flow Switch: See attached vendor literature.

4.

Low Water Cutoff (optional): See attached
vendor literature.

3.4 Inlet Temperature and Temperature

Rise Adjustment

For proper operation the bypass and outlet valves

must be adjusted to obtain the correct heater
temperature rise. Use the following method to set the
bypass assembly at start up:
1.

With all bypass valves open, fire the heater for at
least 10 minutes.  The operating control should
be set at least 5° to 10° F above the pool
temperature to ensure continued operation
throughout this set up procedure.

2.

Observe the thermometer on the inlet header.  To
prevent condensation and damage to the boiler,
the inlet water temperature has to be 100°F.

Содержание MegaTherm MT 1010

Страница 1: ...nance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void t...

Страница 2: ...s 9 2 7 Boiler By Pass Piping 9 2 8 Temperature Sensor Placement and Installation 10 2 9 Automatic Chlorinators 10 SECTION 3 Operation 3 1 Controls General 11 3 2 Initial Start Up 11 3 3 Safety Shutof...

Страница 3: ...he procedures MODEL MT POOL REVISION P PUMP U S Q PUMP CAN HEAT EXCHANGER C GLASS LINED COPPER N GLASS LINES CU NI K BRONZE COPPER S BRONZE CU NI VERSION 1 8 TUBE B 10 TUBE I INDOOR E OUTDOOR FUEL N N...

Страница 4: ...ide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223 1 and any local codes that may be applicable Inadequate...

Страница 5: ...al used to maintain clearances and prevent physical damage and separation of joints Avoid terminating boiler vents near air conditioning or air supply fans The fans can pick up exhausted flue products...

Страница 6: ...a summer exhaust fan Close all fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions for the unit Adjust the thermostat so the appliance will operate c...

Страница 7: ...n Outdoor installations are not recommended in areas where the danger of snow blockage exists WARNING Liquefied petroleum gas is heavier than air Therefore the pool heating boiler should not be instal...

Страница 8: ...rwise 2 The 1825 models are supplied with 3 4 HP pump motors All other models are supplied with 1 2 HP pump motors Consult the National Electrical Code or the Canadian Electrical Code regarding branch...

Страница 9: ...ed by the momentary back siphoning of hot water from the heater when the filter pump stops running The pressure relief valve installed in the tapped opening provided in the outlet header see Figure 9...

Страница 10: ...ic Chlorinators A concentration of chlorine in the heater can be very destructive therefore the following rules about the installation and operation of such devices must be followed 1 The chlorinator...

Страница 11: ...he temperature sensor thermistor is located in the filter circulation piping see Section 2 8 3 Boiler Power On Off Auto Switch This provides for constant or automatic pump operation 4 High Limit Contr...

Страница 12: ...cally lit when the operating controls call for heat If the pilot flame fails for any reason the main valve is shut off within one second and the pilot spark ignition is initiated until the pilot flame...

Страница 13: ...etailed above should be less than 142 F The normal range will be 10 to 37 F higher than the inlet temperature If it exceeds 142 F please contact the Service Department at 800 900 9276 extension 5406 f...

Страница 14: ...ic pools or spa pools are usually piped and controlled so that very warm or hot water often with air injection is forced at high velocity into a confined area of a swimming pool or into a small separa...

Страница 15: ...m are unobstructed 6 Check for fouling on the external surfaces of the heat exchanger every six months NOTE after installation and first start up check the heat exchanger for fouling after the followi...

Страница 16: ...itizing chemicals also adds greatly to the mineral content of the pool If the concentration of minerals in the pool is permitted to become too high the minerals will precipitate out of the water and d...

Страница 17: ...at gas valve terminals Check continuity of actuator burned out or shorted coil If open circuit or short is indicated replace coil or operator G Pump does not run G Operate in manual Check power to pum...

Страница 18: ...Rear 10548401 10548402 10548403 10548404 15 Saddle Assembly End Tile 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 2 2 2 2 2 2 2 2 2 16 Lower End Panel 10540701 1054...

Страница 19: ...MegaTherm Commercial Pool Heating Boiler Page 19 Figure 17 Parts Identification...

Страница 20: ...Assembly Copper Tubes 10534701 10534702 10534703 10534704 10534705 10534706 10534707 Cast Iron Tubs Indoor 8 Tube Assembly Copper Tubes 10542901 10542902 10542903 10542904 10542905 10542906 10542907 B...

Страница 21: ...ll Immersion E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E274000 45 Well High Limit E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 46 Valv...

Страница 22: ...W0034400 W0034400 W0034400 W0034400 Standing Pilot LP Pilot Burner Honeywell W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 IID Pilot Nat Pilot Burner Honeywell W2001...

Страница 23: ...0 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 74 Controller Water Temp E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 75 Sensor Water Temp E2103600...

Страница 24: ...d Spa Page 24 Figure 18 Tile Assemblies When ordering tiles Assembly number is for all tiles Part numbers shown for the front of unit are the same for the rear tiles Check dimensions of old tile as sh...

Страница 25: ...MegaTherm Commercial Pool Heating Boiler Page 25 Figure 19 Outdoor Parts 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 20...

Страница 26: ...03 10658104 10658105 10658106 10658107 10658108 10658109 3 Upper Rear Louver shield 10657101 10657102 10657103 10657104 10657105 10657106 10657107 10657108 10657109 4 Upper Rear Panel 10658701 1065870...

Страница 27: ...1 10659302 10659303 10659304 10659305 10659306 10659307 10659308 10659309 20 Pump Cover Assembly 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 Pump Parts Pump Couple...

Страница 28: ...Pentair Water Commercial Pool and Spa Page 28...

Страница 29: ...MegaTherm Commercial Pool Heating Boiler Page 29...

Страница 30: ...Pentair Water Commercial Pool and Spa Page 30...

Страница 31: ...MegaTherm Commercial Pool Heating Boiler Page 31...

Страница 32: ...000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this document to...

Отзывы: