MegaTherm Commercial Pool Heating Boiler

Page 5

Figure 4. Typical Boiler Installation on Roof

Using 4x4 Stringer.

Figure 5. Installation on Concrete Blocks or Tile.

b. Forced-Air Ventilation

In the United States: any equipment which

exhausts air from the boiler room can deplete the
combustion air supply or reverse the natural draft
action of the venting system. This could cause flue
products to accumulate in the boiler room. Additional
air must be supplied to compensate for such exhaust.
The information in Table 2 is not applicable in
installations where exhaust fans or blowers of any
type are used. Such installations must be designed by
qualified engineers.

In Canada: follow Canadian standard,

CSA-B149.1 or local codes.

If a blower or fan is used to supply air to the

boiler room, the installer should make sure it does not
create drafts which could cause nuisance shutdowns of
the pilot. If a blower is necessary to provide adequate
combustion air to the boiler, a suitable switch or
interlock must be wired into the heater control circuit
to prevent the heater from firing unless the blower is
operating.

The boiler must be completely isolated and

protected from any source of corrosive chemical fumes
such as trichlorethylene, perchloroethylene, chlorine, etc.

2.2.2 Venting

The MegaTherm boiler has a built-in draft

diverter for natural draft operation and must not be
connected to any portion of a mechanical draft system
under positive pressure. The flue outlet must be
connected to a clear, unobstructed vent of adequate
capacity ending above the highest point of the
building with an approved vent cap. The venting
system should be installed according to the latest
edition of ANSI Z223.1 and/or, in Canada,
CSA-B149.1 and any local codes having jurisdiction.

Do not weld or fasten the vent pipe to the boiler

drafthood. The weight of the stack must not rest on the
boiler. The drafthood and boiler top must be easily
removable for normal boiler service and inspection.

IMPORTANT NOTE:

 

Do not use sheet metal

screws at the snap lock joints of Type B gas vents.

Avoid using long horizontal runs of the vent

pipe, and too many 90° elbows, reductions or
restrictions. Horizontal runs should have at least a
1/4" (6mm) rise per foot in the direction of flow. A
vent connector should be supported for the design and
weight of the material used to maintain clearances and
prevent physical damage and separation of joints.

Avoid terminating boiler vents near air

conditioning or air supply fans. The fans can pick up
exhausted flue products from the boiler and return
them inside the building creating a possible health
hazard. A minimum of 4 feet (1.2m), in Canada 6 feet
(1.8m), horizontal distance must be maintained from
electrical meters, gas meters, and relief equipment.

Figure 6. Alcove Installation.

Base must extend out
min. 12" (305mm) on
all sides of
 heater frame.

20 ga. min.
galvanized
sheet metal
 under entire
heater.

Concrete blocks or tile min. 7" (178mm)
high with 3" (76mm) min. air openings.

Blocks must provide solid base and be braced so they
cannot slip out of place. Air openings in blocks must be
arranged to provide unobstructed opening through entire
width or length of base.

* When the ceiling height exceeds 8 feet, you are only allowed to consider 8
feet when calculating the total volume of the enclosure.

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

Water

Heater

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

CLOSET INSTALLATION

(UNACCEPTABLE)

A closet is any 4 sided enclosure
which is less than 16* times the total
volume of all the gas fired appliances
within the enclosure.

ROOM INSTALLATION

(ACCEPTABLE)

A room is any enclosure which is at
least 16* times greater than the total
volume of all the gas fired appliances
within the enclosure.

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

12345678901234567890

Water

Heater

ALCOVE INSTALLATION

(ACCEPTABLE)

An alcove suitable for the installation
of a water heater is a restricted section
of a room not separated from the
room by a door or partition and which
meets the minimum clearances for
the specific model water heater listed
below.

Содержание MegaTherm MT 1010

Страница 1: ...nance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void t...

Страница 2: ...s 9 2 7 Boiler By Pass Piping 9 2 8 Temperature Sensor Placement and Installation 10 2 9 Automatic Chlorinators 10 SECTION 3 Operation 3 1 Controls General 11 3 2 Initial Start Up 11 3 3 Safety Shutof...

Страница 3: ...he procedures MODEL MT POOL REVISION P PUMP U S Q PUMP CAN HEAT EXCHANGER C GLASS LINED COPPER N GLASS LINES CU NI K BRONZE COPPER S BRONZE CU NI VERSION 1 8 TUBE B 10 TUBE I INDOOR E OUTDOOR FUEL N N...

Страница 4: ...ide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223 1 and any local codes that may be applicable Inadequate...

Страница 5: ...al used to maintain clearances and prevent physical damage and separation of joints Avoid terminating boiler vents near air conditioning or air supply fans The fans can pick up exhausted flue products...

Страница 6: ...a summer exhaust fan Close all fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions for the unit Adjust the thermostat so the appliance will operate c...

Страница 7: ...n Outdoor installations are not recommended in areas where the danger of snow blockage exists WARNING Liquefied petroleum gas is heavier than air Therefore the pool heating boiler should not be instal...

Страница 8: ...rwise 2 The 1825 models are supplied with 3 4 HP pump motors All other models are supplied with 1 2 HP pump motors Consult the National Electrical Code or the Canadian Electrical Code regarding branch...

Страница 9: ...ed by the momentary back siphoning of hot water from the heater when the filter pump stops running The pressure relief valve installed in the tapped opening provided in the outlet header see Figure 9...

Страница 10: ...ic Chlorinators A concentration of chlorine in the heater can be very destructive therefore the following rules about the installation and operation of such devices must be followed 1 The chlorinator...

Страница 11: ...he temperature sensor thermistor is located in the filter circulation piping see Section 2 8 3 Boiler Power On Off Auto Switch This provides for constant or automatic pump operation 4 High Limit Contr...

Страница 12: ...cally lit when the operating controls call for heat If the pilot flame fails for any reason the main valve is shut off within one second and the pilot spark ignition is initiated until the pilot flame...

Страница 13: ...etailed above should be less than 142 F The normal range will be 10 to 37 F higher than the inlet temperature If it exceeds 142 F please contact the Service Department at 800 900 9276 extension 5406 f...

Страница 14: ...ic pools or spa pools are usually piped and controlled so that very warm or hot water often with air injection is forced at high velocity into a confined area of a swimming pool or into a small separa...

Страница 15: ...m are unobstructed 6 Check for fouling on the external surfaces of the heat exchanger every six months NOTE after installation and first start up check the heat exchanger for fouling after the followi...

Страница 16: ...itizing chemicals also adds greatly to the mineral content of the pool If the concentration of minerals in the pool is permitted to become too high the minerals will precipitate out of the water and d...

Страница 17: ...at gas valve terminals Check continuity of actuator burned out or shorted coil If open circuit or short is indicated replace coil or operator G Pump does not run G Operate in manual Check power to pum...

Страница 18: ...Rear 10548401 10548402 10548403 10548404 15 Saddle Assembly End Tile 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 2 2 2 2 2 2 2 2 2 16 Lower End Panel 10540701 1054...

Страница 19: ...MegaTherm Commercial Pool Heating Boiler Page 19 Figure 17 Parts Identification...

Страница 20: ...Assembly Copper Tubes 10534701 10534702 10534703 10534704 10534705 10534706 10534707 Cast Iron Tubs Indoor 8 Tube Assembly Copper Tubes 10542901 10542902 10542903 10542904 10542905 10542906 10542907 B...

Страница 21: ...ll Immersion E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E274000 45 Well High Limit E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 46 Valv...

Страница 22: ...W0034400 W0034400 W0034400 W0034400 Standing Pilot LP Pilot Burner Honeywell W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 IID Pilot Nat Pilot Burner Honeywell W2001...

Страница 23: ...0 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 74 Controller Water Temp E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 75 Sensor Water Temp E2103600...

Страница 24: ...d Spa Page 24 Figure 18 Tile Assemblies When ordering tiles Assembly number is for all tiles Part numbers shown for the front of unit are the same for the rear tiles Check dimensions of old tile as sh...

Страница 25: ...MegaTherm Commercial Pool Heating Boiler Page 25 Figure 19 Outdoor Parts 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 20...

Страница 26: ...03 10658104 10658105 10658106 10658107 10658108 10658109 3 Upper Rear Louver shield 10657101 10657102 10657103 10657104 10657105 10657106 10657107 10657108 10657109 4 Upper Rear Panel 10658701 1065870...

Страница 27: ...1 10659302 10659303 10659304 10659305 10659306 10659307 10659308 10659309 20 Pump Cover Assembly 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 Pump Parts Pump Couple...

Страница 28: ...Pentair Water Commercial Pool and Spa Page 28...

Страница 29: ...MegaTherm Commercial Pool Heating Boiler Page 29...

Страница 30: ...Pentair Water Commercial Pool and Spa Page 30...

Страница 31: ...MegaTherm Commercial Pool Heating Boiler Page 31...

Страница 32: ...000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this document to...

Отзывы: