MegaTherm Commercial Pool Heating Boiler

Page 9

IMPORTANT NOTE:

 The pool filter pump and

boiler must be electrically interlocked so the boiler
cannot come on unless the pump is running and there
is full flow in the filter piping where the boiler is
connected. If the pool filter pump operation is
intermittent the boiler must be shut off prior to pump
shutdown. See paragraph heading Auxiliary Time
Clock Wiring below. If the backwash operation is
manual the boiler must be shut off manually during
backwashing.

Auxiliary Time Clock Wiring:

If a time clock is used to control the filter pump

operation, a separate switch or relay must be used to
shut off the boiler at least 15 minutes before the filter
pump is shut off. Wire the switch or relay (often called
the Fireman Switch) to the terminals shown in the
wiring diagram as “Field Interlock.”
4.

All field installed electrical safety devices and all
field installed controllers (valve end switches,
draft switches, relays, timers) can be connected
to the boiler control to the terminals shown in the
wiring diagram designated “Field Interlock.”

5.

Field location of the temperature sensor is
described in Section 2.8.
Where the boiler is installed with a draft fan refer

to the fan manufacturer's wiring diagram. The draft
switch should be wired across the field interlock
terminals in the boiler control panel.

2.6 General Piping Instructions

In addition to the bypass valve “B” and outlet

valve “A” shown in Figure 10, an inlet valve “C”
should be provided so that the heater can be readily
isolated for service. All valves should be butterfly or
ball style, not gate valves. For spas application see
Section 3.9.

Since heater outlet temperatures can reach

150°F (66°C) in some cases, copper or CPVC are
recommended materials for heater connection piping.
PVC material may be used for the inlet valve and the
piping upstream of it.

Figure 9.  Pressure Relief Valve Location.

When pipe, fittings, grids or any other element of

the filter system are made of plastic materials, they
may be damaged by the momentary "back siphoning"
of hot water from the heater when the filter pump
stops running.

The pressure relief valve installed in the tapped

opening provided in the outlet header (see Figure 9),
must be piped, but not connected, to a drain or floor
sink. The drain pipe must be the same size as the valve
outlet and must pitch downward from the valve.
Where no special setting of the relief valve is ordered,
the factory will furnish a 75 psi setting.

The pressure relief valve lever must be tripped at

least once a year to insure that waterways are clean.
When manually operating lever, water will discharge
through the drain line. Precautions must be taken to
avoid contact with hot water and water damage.

2.7 Boiler By-Pass Piping

All MT series boilers, 500-1825 models, must be

installed with bypass piping. Please use Figure 10 as
your guide to plumb the bypass. For spas see Section
3.9.

The diverter valve in the main line, shown in

dashed line in Figure 11, is optional and may be
needed only if the distance to the heater is over 15'.
Call the Service Department at 800-900-9276,
extension 5406 for assistance.

All models are supplied with integral pumps,

These pumps are sized for the pressure drop through
the heat exchanger, 30 feet of piping and through the
bypass piping as shown in Figure 10.

Any deviations from  the arrangement shown

may reduce flow, hinder performance, and will void
the warranty.

2½ inch NPT piping is shown, however, models

500I-1430I and models 500E-1010E may be installed
using 2 inch NPT piping.

All models must be installed in the primary-

secondary arrangement shown. The boiler loop piping
must tee into the filter loop piping with the inlet and
outlet connection spaced a maximum of 18" (450mm)
apart (see Figure 10).

To insure that pool inlet water does not exceed

104°F, the filter pump loop must circulate at the
minimum flow rates shown in Table 4.

The outlet valve “A” and the bypass valve “B”

must have a provision for locking the handles in place
(or removing them) after the temperature rise and inlet
temperature adjustments have been made.

Boiler Model

Minimum Filter Pump Flow Rate

500-850

90 GPM

1010-1200

110 GPM

1430

140 GPM

1670-1825

180 GPM

Table 4. Minimum Flow to Supply Heater Loop.

Содержание MegaTherm MT 1010

Страница 1: ...nance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void t...

Страница 2: ...s 9 2 7 Boiler By Pass Piping 9 2 8 Temperature Sensor Placement and Installation 10 2 9 Automatic Chlorinators 10 SECTION 3 Operation 3 1 Controls General 11 3 2 Initial Start Up 11 3 3 Safety Shutof...

Страница 3: ...he procedures MODEL MT POOL REVISION P PUMP U S Q PUMP CAN HEAT EXCHANGER C GLASS LINED COPPER N GLASS LINES CU NI K BRONZE COPPER S BRONZE CU NI VERSION 1 8 TUBE B 10 TUBE I INDOOR E OUTDOOR FUEL N N...

Страница 4: ...ide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223 1 and any local codes that may be applicable Inadequate...

Страница 5: ...al used to maintain clearances and prevent physical damage and separation of joints Avoid terminating boiler vents near air conditioning or air supply fans The fans can pick up exhausted flue products...

Страница 6: ...a summer exhaust fan Close all fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions for the unit Adjust the thermostat so the appliance will operate c...

Страница 7: ...n Outdoor installations are not recommended in areas where the danger of snow blockage exists WARNING Liquefied petroleum gas is heavier than air Therefore the pool heating boiler should not be instal...

Страница 8: ...rwise 2 The 1825 models are supplied with 3 4 HP pump motors All other models are supplied with 1 2 HP pump motors Consult the National Electrical Code or the Canadian Electrical Code regarding branch...

Страница 9: ...ed by the momentary back siphoning of hot water from the heater when the filter pump stops running The pressure relief valve installed in the tapped opening provided in the outlet header see Figure 9...

Страница 10: ...ic Chlorinators A concentration of chlorine in the heater can be very destructive therefore the following rules about the installation and operation of such devices must be followed 1 The chlorinator...

Страница 11: ...he temperature sensor thermistor is located in the filter circulation piping see Section 2 8 3 Boiler Power On Off Auto Switch This provides for constant or automatic pump operation 4 High Limit Contr...

Страница 12: ...cally lit when the operating controls call for heat If the pilot flame fails for any reason the main valve is shut off within one second and the pilot spark ignition is initiated until the pilot flame...

Страница 13: ...etailed above should be less than 142 F The normal range will be 10 to 37 F higher than the inlet temperature If it exceeds 142 F please contact the Service Department at 800 900 9276 extension 5406 f...

Страница 14: ...ic pools or spa pools are usually piped and controlled so that very warm or hot water often with air injection is forced at high velocity into a confined area of a swimming pool or into a small separa...

Страница 15: ...m are unobstructed 6 Check for fouling on the external surfaces of the heat exchanger every six months NOTE after installation and first start up check the heat exchanger for fouling after the followi...

Страница 16: ...itizing chemicals also adds greatly to the mineral content of the pool If the concentration of minerals in the pool is permitted to become too high the minerals will precipitate out of the water and d...

Страница 17: ...at gas valve terminals Check continuity of actuator burned out or shorted coil If open circuit or short is indicated replace coil or operator G Pump does not run G Operate in manual Check power to pum...

Страница 18: ...Rear 10548401 10548402 10548403 10548404 15 Saddle Assembly End Tile 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 2 2 2 2 2 2 2 2 2 16 Lower End Panel 10540701 1054...

Страница 19: ...MegaTherm Commercial Pool Heating Boiler Page 19 Figure 17 Parts Identification...

Страница 20: ...Assembly Copper Tubes 10534701 10534702 10534703 10534704 10534705 10534706 10534707 Cast Iron Tubs Indoor 8 Tube Assembly Copper Tubes 10542901 10542902 10542903 10542904 10542905 10542906 10542907 B...

Страница 21: ...ll Immersion E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E2074000 E274000 45 Well High Limit E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 E0025900 46 Valv...

Страница 22: ...W0034400 W0034400 W0034400 W0034400 Standing Pilot LP Pilot Burner Honeywell W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 W0034300 IID Pilot Nat Pilot Burner Honeywell W2001...

Страница 23: ...0 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 E2103900 74 Controller Water Temp E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 E2103800 75 Sensor Water Temp E2103600...

Страница 24: ...d Spa Page 24 Figure 18 Tile Assemblies When ordering tiles Assembly number is for all tiles Part numbers shown for the front of unit are the same for the rear tiles Check dimensions of old tile as sh...

Страница 25: ...MegaTherm Commercial Pool Heating Boiler Page 25 Figure 19 Outdoor Parts 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 20...

Страница 26: ...03 10658104 10658105 10658106 10658107 10658108 10658109 3 Upper Rear Louver shield 10657101 10657102 10657103 10657104 10657105 10657106 10657107 10657108 10657109 4 Upper Rear Panel 10658701 1065870...

Страница 27: ...1 10659302 10659303 10659304 10659305 10659306 10659307 10659308 10659309 20 Pump Cover Assembly 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 20050100 Pump Parts Pump Couple...

Страница 28: ...Pentair Water Commercial Pool and Spa Page 28...

Страница 29: ...MegaTherm Commercial Pool Heating Boiler Page 29...

Страница 30: ...Pentair Water Commercial Pool and Spa Page 30...

Страница 31: ...MegaTherm Commercial Pool Heating Boiler Page 31...

Страница 32: ...000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this document to...

Отзывы: