Wiring the Pump

To connect the IntelliFlo

® 

VS+SVRS

 

Pump to an AC power source:

1.  Make sure all electrical breakers and switches are turned off before wiring motor.
2.  Make sure that the wiring voltage is 230 VAC ± 10%.
3.   Use #12 AWG for wire runs up to 100 feet (30.5 meters) and #10 AWG for lengths longer than 

100 feet (30.5 meters).  When in doubt use a heavier gauge (larger diameter) wire. Heavier gauge 

will allow the motor to run cooler and more efficient.

4.  Make sure all electrical connections are clean and tight.

5.  Cut the wires to the appropriate length so they do not overlap or touch when connected.

6.  Permanently ground the motor using the green ground wire, as shown below. Use the correct wire 

size and type specified by National Electrical Code. Make sure the ground wire is connected to an 

electrical service ground.

7.  Bond the motor to the pool structure in accordance with the National Electrical Code. Use a solid          

No. 8 AWG or larger copper conductor (No. 6 or larger in Canada). Run a wire from the external 

bonding lug to the pool bonding structure, as shown below.

8.  The pump should be permanently connected to either a 

circuit breaker

2-pole timer

 or 

2-pole relay

If AC power is supplied by a GFCI circuit breaker, use a dedicated circuit breaker that has no other 

electrical loads.

9. 

IMPORTANT: When connecting the pump to an automation system ( IntelliTouch

®

, EasyTouch

®

 

or SunTouch

® 

Control System and IntelliComm

®

 Communication Center), continuous power 

must be supplied to the pump by connecting it directly to the circuit breaker. When using an 

automation system,  be sure that no other lights or appliances are on the same circuit. 

 

NOTE:  When the pump is started and stopped by removing power with a relay or timer, 
a two-pole device should be used to apply and remove power to both POWER LINE TERMINALS.

BONDING LUG

GROUND WIRE 

CONNECTION

Initial SVRS Setup and Operational Check

The following initial SVRS setup steps describe how to determine the maximum intended flow 

(GPM) and pump speed (RPM) for the system, and to perform a simulated entrapment event. 

1.  The SVRS system should be initially setup for operation at maximum flow (see page 12).

2.   If the system includes a filter, the filter must be in a clean condition prior to setting up the 

maximum flow condition.

3.   Remove the drain plug from the pump strainer housing and install the vacuum gage into the 1/4” 

NPT housing opening.

Содержание IntelliFlo VS+SVRS

Страница 1: ...RS INTELLIPRO VS SVRS ULTRA ENERGY EFFICIENT PUMP WITH SAFETY VACUUM RELEASE SYSTEM SVRS PROTECTION IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS INSTALLATION...

Страница 2: ...is subject to change without notice 1620 Hawkins Ave Sanford NC 27330 919 566 8000 10951 West Los Angeles Ave Moorpark CA 93021 805 553 5000 All Pentair trademarks and logos are owned by Pentair or o...

Страница 3: ...Pump Overview Variable Speed Pump Remote Control Features Motor Assembly Motor Features Drive Assembly and Control Panel Section 2 Operator Control Panel Operator Control Panel Controls and LEDs Secti...

Страница 4: ...on a broken or uncovered pool drain or hair entanglements This pump is not a substitute for properly installed and secured pool drain covers An ANSI ASME A112 19 8 approved anti entrapment drain cove...

Страница 5: ...eparation Stand clear of all circulation system equipment when turning on or starting up pump Before servicing equipment make note of the filter pressure Be sure that all controls are set to ensure th...

Страница 6: ...h for the pump must be in an easily accessible obvious place Make sure users know where it is located and how to use it in case of emergency Install the pump a minimum of five 5 feet from the inside w...

Страница 7: ...Installation of Electrical Controls at Equipment Pad ON OFF Switches Timers and Automation Load Center READ AND KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE Install all electrical controls at equipme...

Страница 8: ...emperature over current suction blockage and freeze protection with user defined minimum and maximum speed presets This pump is intended to be used as part of a complete pool safety system It complies...

Страница 9: ...y ETL SVRS feature accommodates flooded and elevated suction for pump with suction levels at pump strainer at 25 mercury Hg SVRS feature requires no special plumbing or electrical connections Features...

Страница 10: ...main motor shaft seal assists in slinging water away from the shaft opening in the flange Drive assembly and electronics enclosure Pump Assembly Motor fan cover Communication port for connection to Ea...

Страница 11: ...ts of an operator control panel and the system electronics that drive the motor The drive microprocessor controls the motor by changing the frequency of the current it receives together with changing...

Страница 12: ...ters edit mode for changing a value on line two of the display Escape button Moves to next level up in the menu structure and or stops editing the current setting Menu button Accesses the menu items i...

Страница 13: ...n the LED is on the pump is currently running or in a mode to start automatically Reset button Reset alarm or alert LEDs On This green power LED is on when pump is powered on Warning LED is on if a wa...

Страница 14: ...tion cable is connected Servicing Equipment Disconnect Power to Pump When servicing equipment filters heaters chlorinators etc disconnect the communication cable and switch OFF circuit breaker to remo...

Страница 15: ...manually selected speed until the next scheduled speed program 2 Egg Timer Duration Speeds 1 4 can be programmed to run for a duration of time once pressed This means that the Speed button is pressed...

Страница 16: ...to 10 hrs Default 3 hours 1 min to 30 min Default 11 minutes Disabled Enabled Default Enabled Speed Default 2350 RPM Speed Default 3110 RPM English Default English Schedule Set Speed Set Start Time Se...

Страница 17: ...d 3 Press the Select button Pump Address is displayed The Factory default setting is address 1 4 To change the pump address press the Select button The first digit 1 selected 5 Press Up or Down arrow...

Страница 18: ...the green power LED is on 2 Press the Menu button Settings is displayed 3 Press the Select button Pump Address is displayed 4 Use the Up or Down arrow button to scroll to Temperature Units menu item...

Страница 19: ...inimum speed setting from 1100 to 1700 RPM 7 Press the Enter button to save the setting To cancel any changes press the Escape button to exit edit mode without saving 8 Press the Escape button to exit...

Страница 20: ...n the pump shuts down for a blockage alarm it will not automatically restart The pump will have to be manually restarted by pressing the RESET button and the START STOP button To access the SVRS Auto...

Страница 21: ...t arrow button to move cursor and press up and down arrow to change password number to desired setting 15 Press the Enter button to save the setting To cancel any changes press the Escape button to ex...

Страница 22: ...wait 5 seconds and then move to 2300 RPM wait five 5 seconds then move to 2350 RPM This adjustment is made available to the user to help minimize the occurrence of a false tripping SVRS alarm when sw...

Страница 23: ...Select to highlight manual Speeds 5 8 default setting is DISABLED To create a schedule for speed 5 8 Press Select to highlight Disabled 7 Use the Up or Down arrow button to scroll to Schedule 8 Press...

Страница 24: ...is displayed 3 Use the Up or Down arrow button to scroll to Ext Ctrl 5 Press the Select button Program 1 is displayed 6 Press the Select button 1100 RPM is displayed 7 Press the Select button The RPM...

Страница 25: ...to exit without saving 15 Press the Escape button to exit Features Time Out This feature keeps the IntelliFlo VS SVRS Pump from running for a programmable amount of time This feature can be used to a...

Страница 26: ...alarm occurs Note When a Priming Dry Alarm takes place it will try to restart after 10 minutes unlike a pump which will not restart after a Priming Dry Alarm Primed Sensitivity The primed sensitivity...

Страница 27: ...ill read Primed Sensitivity The default for this setting being 1 12 Press the Select button to change the setting The cursor will highlight the number 13 Use the up or Down arrow button to change the...

Страница 28: ...utton Settings is displayed 3 Use the Down arrow button to scroll to AntiFreeze 4 Press the Select button The factory default is AntiFreeze Enabled 5 To disable AntiFreeze Press the Select button Enab...

Страница 29: ...ause property damage and personal injury Do not add chemicals to the system directly in front of pump suction Adding undiluted chemicals may damage the pump and will void the warranty Open gate valves...

Страница 30: ...lid in a counterclockwise direction until it stops and remove them 2 Fill the pump strainer pot with water 3 Check the system and ensure water has an open path for free system flow 4 Reinstall the pu...

Страница 31: ...highest number will be communicated to the pump The IntelliComm communication center will always communicate to pump using ADDRESS 1 Program number priority is as follows Example If programs 1 and 2...

Страница 32: ...ontrol system will not start communicating with the pump until the pump is assigned to a circuit The pump s default pump address is one 1 which is the only address that works with EasyTouch system See...

Страница 33: ...ews 8 EasyTouch control system to pump pin configuration Pump Connect pin 6 green to EasyTouch screw terminal pin 2 green Pump Connect pin 7 yellow to EasyTouch screw terminal pin 3 yellow 9 Insert th...

Страница 34: ...screw High voltage cover panel Retaining screw 10 Close the control panel into its original position and secure it with the two access screws 11 Install the high voltage cover panel and secure it with...

Страница 35: ...s is assigned to a circuit The pump s default pump address is one See page 10 for details about how to check the pump address and change if necessary For more information refer to the IntelliTouch Use...

Страница 36: ...Pump to IntelliTouch control system pin configuration Pump Connect pin 6 green to IntelliTouch screw terminal pin 2 green Pump Connect pin 7 yellow to IntelliTouch screw terminal pin 3 yellow 7 Close...

Страница 37: ...up through the power center grommet opening located on the left side and up through the low voltage raceway to the motherboard 4 Strip back the cable conductors in Insert the wires into the screw term...

Страница 38: ...al injury In order to avoid the possibility of personal injury make sure the suction and discharge valves are open and that the strainer pot is cool to the touch then open with extreme caution To prev...

Страница 39: ...rom the filter until a steady stream of water comes out 16 Close the manual air relief valve Motor Service 1 Protect from heat Shade the motor and controller from the sun Any enclosure must be well ve...

Страница 40: ...ng on page 22 Winterizing To protect the IntelliFlo VS SVRS Pump electronics from damage due to freezing conditions the pump will switch it self on to generate internal heat when the air temperature d...

Страница 41: ...34 INTELLIFLO VS SVRS and INTELLIPRO VS SVRS Variable Speed Pump Installation and User s Guide Blank Page...

Страница 42: ...Install the pump in a well ventilated location protected from excessive moisture i e rain gutter downspouts sprinklers etc 6 For hot tubs and spas do not install within an outer enclosure or beneath...

Страница 43: ...structure as shown below 8 The pump should be permanently connected to either a circuit breaker 2 pole timer or 2 pole relay If AC power is supplied by a GFCI circuit breaker use a dedicated circuit b...

Страница 44: ...the main panel 2 Disconnect the RS 485 communication cable from the pump 3 Drain the pump by removing the drain plugs 4 Remove the six bolts that hold the main pump body strainer pot volute to the rea...

Страница 45: ...amic and carbon faces with a clean cloth 3 Remount the seal plate to the motor 4 Grease the motor shaft thread and screw impeller onto the motor shaft 5 Screw in the impeller lock screw counterclockwi...

Страница 46: ...n keeping moisture out of the drive and motor Replace the gasket if damaged Do not reassemble with a damaged or missing gasket To install the pump s drive assembly onto the motor assembly 1 Make sure...

Страница 47: ...IntelliFlo VS SVRS Pump StaRite P N P6E6XS4H 209L IntelliPro VS SVRS Pump Description BASKET AQ WF BOLT HEX HD 3 8 16 x 7 8 S S QTY4 BOLT 3 8 16X 1 1 4 HEX CAP 18 8 S S QTY4 BOLT 3 8 16X2 HEX CAP 18...

Страница 48: ...ce at the Electrical Panel Input 230 VAC 50 60 Hz 3200 Watts Flow and Power vs Flow Pump Curve Feet of Water U S Gallons per Minute Cubic Meters per Hour TOTAL HEAD Meters of Water 3110 RPM 2350 RPM 1...

Страница 49: ...42 INTELLIFLO VS SVRS and INTELLIPRO VS SVRS Variable Speed Pump Installation and User s Guide Blank Page...

Страница 50: ...E portion of the IntelliTouch Control System s appropriate circuit function menu To re enable the pump s internal antifreeze protection the power to the drive must be cycled off then back on Blocked s...

Страница 51: ...arning on page 43 Air pockets or leaks in suction line PRIME ERROR may be displayed Clogged impeller PRIME ERROR may be displayed Pump strainer clogged PRIME ERROR may be displayed Check suction pipin...

Страница 52: ...ping is too small Check and clean pool filter Increase filtration run time Electrical problem For IntelliFlo pump alert display messages refer to Alerts and Warning on page 43 Could appear as a Low Vo...

Страница 53: ...also consider the amount of water moved for the cost incurred Water to Wire Efficiency The pump cannot be matched in today s industry for flow versus continuous watts at any speed by any other pump i...

Страница 54: ...ing is needed In addition to chemical testing a good way to check your water clarity is that the main drain cover should be clearly visible from the deck Automatic pool sweeps booster pump style Usual...

Страница 55: ...lp maintain heating efficiency Energy Efficient When its time to replace your old motor and IntelliFlo VS SVRS Pump assembly consider using a variable speed energy efficient pump It moves more water m...

Страница 56: ...00 10951 WEST LOS ANGELES AVE MOORPARK CA 93021 805 553 5000 WWW PENTAIRPOOL COM 2014 Pentair Water Pool and Spa Inc All rights reserved This document is subject to change without notice P N 353850 RE...