Page 7
Timer Operation
System 7
Alternating (2 Valves)
During normal operation the Time of Day display alternates with the Volume Remaining display
(gallons or m3). The Volume Remaining is for the individual unit.
— As treated water is used, the Volume Remaining display counts down from the calculated capacity to
zero or (----). When this occurs a Regeneration Cycle queues.
— The valve requiring Regeneration sends a lock command to the standby valve. The standby valve goes
to In Service and exhausted valve starts a Regeneration Cycle.
— If a valve is in Regeneration and the other valve exhausts its volume remaining, then the exhausted
valve remains In Service with Regeneration queued until the other valve goes into standby. The
exhausted valve goes into standby after completing Regeneration.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
System 9
Alternating (2 – 4 Valves)
During normal operation the Time of Day display alternates with the Volume Remaining display
(gallons or m3). The Volume Remaining is for the individual unit.
— As treated water is used, the Volume Remaining display counts down from the calculated capacity to
zero or (----). When this occurs a Regeneration Cycle queues.
— The valve requiring Regeneration sends a lock command to the standby valve. The standby valve goes
to In Service and exhausted valve starts a Regeneration Cycle.
— If a valve is in Regeneration and another valve exhausts its volume remaining, then the exhausted
valve remains In Service with Regeneration queued until the other valve goes into standby. The
exhausted valve goes into standby after completing Regeneration.
— All units remain In Service except those in standby or Regeneration.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship to flow rate.
Important System Operations Tips
• When programming multi-unit systems, program LAg units first and then LEAd unit. This eliminates or
minimizes program and communication errors.
• When changing a valve from one system type to another system type, perform a Master Reset first.
• System 6, 7 and 9 valves coming out of program mode or on power-up calculate their volume
(display = CALc) and then wait for a good communication signal.
— When a good communication signal is received, the system resume normal operations.
— If the system does not receive a good communication signal, CALc displays and the system goes into
a wait. Press the EC key to force the system out of the wait and resume normal operation. A
communication error may appear after one minute.
• The System 4, 5 and 6 LEAd valve drive sequence going into Regeneration is:
— The lower drive moves to off-line and the upper drive moves to first Regeneration position.
• All system 7 and 9 valves:
— The off-line valve moves to online, the valve requiring Regeneration moves its lower drive to off-line
and then the upper drive moves to first Regeneration position.
• Reserve capacity–System 4Fd only. After power-up or Master Reset, the reserve is set by using the
safety factor. Reserve is limited to a range of 0% - 50% of the unit capacity.
• System 6 and 7, LEAd units only, respond to remote lock and chemical pump. Also chemical pump is
available only if the auxiliary relay in regeneration is not used [AroF]
Содержание Fleck 3200NT
Страница 1: ...3200NT Service Manual IMPORTANT Fill in Pertinent Information on Page 3 for Future Reference...
Страница 25: ...Page 25 Notes...
Страница 26: ...Page 26 Power Head Assembly 2750 2850 2900 Upper Drive and 2900 Lower Drive...
Страница 28: ...Page 28 Power Head Assembly 3150 3900 Upper Drive and 3900 Lower Drive...
Страница 36: ...Page 36 2750 2850 Timer Wiring Diagram...
Страница 37: ...Page 37 3150 Timer Wiring Diagram...
Страница 38: ...Page 38 2900 Timer Wiring Diagram...
Страница 39: ...Page 39 3900 Timer Wiring Diagram...
Страница 40: ...Page 40 3200NT Remote Timer Wiring Diagram 42073_REVA...
Страница 41: ...Page 41 2750 2850 3200NT Remote Wiring Diagram 42074_REVA...
Страница 42: ...Page 42 3150 3200NT Remote Wiring Diagram 42076_REVA...
Страница 43: ...Page 43 2900 3200NT Remote Wiring Diagram 42075_REVA...
Страница 44: ...Page 44 3900 3200NT Remote Wiring Diagram 42077_REVA...
Страница 49: ...Page 49 Notes...
Страница 50: ...Page 50 Notes...
Страница 51: ...Page 51 Notes...
Страница 52: ...P N 41093 Rev E 9 06...