Master Programming Mode
5. Remote Signal Start (Display Code rS)
The control valve is monitored other than a meter. Regeneration begins immediately after a contact closure
is received for the number of minutes programmed. The amount of time is required for a contact closure to
be presented before the signal is considered to be valid.
Range = 1 – 99 minutes
Cancel Setting
Setting: [rSoF]
3-Minute Signal Time To Start Regeneration
Setting: [rS-3]
— Use Set Up or Set Down buttons to adjust this value.
— Press the Extra Cycle button.
6. Gallons / Meter3 Display Format (Display Code U)
This program step sets the desired display format. The letter U in the first digit of the display identifies
this program step. The possible settings include:
.
Gallons of water, 12 hour timekeeping, and grains of hardness
Setting: [ U - - 1 ]
M3 of water, 24 hour timekeeping, and degrees of hardness
Setting: [ U - - 4 ]
— Use Set Up or Set Down buttons to adjust this value.
— Press the Extra Cycle button.
7. Unit Capacity (Display Code C)
This program step sets the capacity of the system in kilograins (or m3 X degrees for metric systems). The
letter C in the first digit of the display identifies this program step. System Capacity calculates the amount
of treated water (gallons or liters) that can be treated by the unit before a regeneration cycle is required.
Range = C--9 – C999 kilograins (US [U - -1])
Range = Ct1.0 – Ct2.9 thousands of kilograins or millions of grains (US [U - -1])
Range = C199 – C999 m3 X degrees (metric [U - - 4])
Range = Ct1.0 – Ct19 kilo m3 X degrees (metric [U - - 4])
450,000 grain system capacity, US display
Setting: [ C 450]
— Use Set Up or Set Down buttons to adjust this value.
— Press the Extra Cycle button.
8. Capacity Safety Factor (Display Code cF)
This program step adjusts system capacity. The setting is a percentage by which the unit’s capacity is
reduced.
Range = 0 – 50%.
Reduce system capacity by 10%
Setting: [ cF10 ]
— Use Set Up or Set Down buttons to adjust this value.
— Press the Extra Cycle button.
CAUTION: Before entering Master Programming, please contact your local professional water dealer.
Содержание Fleck 3200NT
Страница 1: ...3200NT Service Manual IMPORTANT Fill in Pertinent Information on Page 3 for Future Reference...
Страница 25: ...Page 25 Notes...
Страница 26: ...Page 26 Power Head Assembly 2750 2850 2900 Upper Drive and 2900 Lower Drive...
Страница 28: ...Page 28 Power Head Assembly 3150 3900 Upper Drive and 3900 Lower Drive...
Страница 36: ...Page 36 2750 2850 Timer Wiring Diagram...
Страница 37: ...Page 37 3150 Timer Wiring Diagram...
Страница 38: ...Page 38 2900 Timer Wiring Diagram...
Страница 39: ...Page 39 3900 Timer Wiring Diagram...
Страница 40: ...Page 40 3200NT Remote Timer Wiring Diagram 42073_REVA...
Страница 41: ...Page 41 2750 2850 3200NT Remote Wiring Diagram 42074_REVA...
Страница 42: ...Page 42 3150 3200NT Remote Wiring Diagram 42076_REVA...
Страница 43: ...Page 43 2900 3200NT Remote Wiring Diagram 42075_REVA...
Страница 44: ...Page 44 3900 3200NT Remote Wiring Diagram 42077_REVA...
Страница 49: ...Page 49 Notes...
Страница 50: ...Page 50 Notes...
Страница 51: ...Page 51 Notes...
Страница 52: ...P N 41093 Rev E 9 06...