Page 5
Timer Operation
Immediate Regeneration Timer with Regeneration Day Override Set
When the valve reaches the set Days Since Regeneration Override value, a Regeneration Cycle initiates immedi-
ately. This occurs even if the Volume Remaining display has not reached zero.
Delayed Regeneration Timer with Regeneration Day Override Set
When the timer reaches the set Days Since Regeneration Override value a Regeneration Cycle initiates at the
preset Regeneration Time. This occurs even if the Volume Remaining display has not reached zero.
Timer Operation During Programming
The timer only enters the Program Mode with the timer In Service. While in the Program Mode the timer continues
to operate normally monitoring water usage and keeping all displays up to date. Timer programming is stored in
memory permanently. There is no need for battery backup power.
Timer Operation During A Power Failure
During a power failure all timer displays and programming are stored for use upon power re-application. The timer
retains all values, without loss. The timer is fully inoperative and any calls for regeneration are delayed. The timer,
upon power re-application, resumes normal operation from the point that it was interrupted.
NOTE: An inaccurate Time of Day display may indicate a power outage
Remote Lockout
The timer does not allow the unit/system to go into Regeneration until the Regeneration Lockout Input signal to
the unit/system is cleared. This requires a contact closure to activate. The recommended gauge wire is 20 with a
maximum length of 500 feet. See P4 remote inputs in the wiring diagrams on pages 16 - 20.
Remote Signal Start Regeneration
The control valve monitors treated water other than a flow meter. When timer receives a contact closure for the
programmed amount of time, regeneration begins. The recommended gauge wire is 20 with a maximum length of
500 feet. See P4 remote inputs in the wiring diagrams on pages 16 - 20.
Day Override Feature
If the Day Override option is turned on and the valve reaches the set Regeneration Day Override value without
the water meter initiating a Regeneration Cycle, a Regeneration Cycle queues. This occurs regardless of the
remaining volume available.
Содержание Fleck 3200NT
Страница 1: ...3200NT Service Manual IMPORTANT Fill in Pertinent Information on Page 3 for Future Reference...
Страница 25: ...Page 25 Notes...
Страница 26: ...Page 26 Power Head Assembly 2750 2850 2900 Upper Drive and 2900 Lower Drive...
Страница 28: ...Page 28 Power Head Assembly 3150 3900 Upper Drive and 3900 Lower Drive...
Страница 36: ...Page 36 2750 2850 Timer Wiring Diagram...
Страница 37: ...Page 37 3150 Timer Wiring Diagram...
Страница 38: ...Page 38 2900 Timer Wiring Diagram...
Страница 39: ...Page 39 3900 Timer Wiring Diagram...
Страница 40: ...Page 40 3200NT Remote Timer Wiring Diagram 42073_REVA...
Страница 41: ...Page 41 2750 2850 3200NT Remote Wiring Diagram 42074_REVA...
Страница 42: ...Page 42 3150 3200NT Remote Wiring Diagram 42076_REVA...
Страница 43: ...Page 43 2900 3200NT Remote Wiring Diagram 42075_REVA...
Страница 44: ...Page 44 3900 3200NT Remote Wiring Diagram 42077_REVA...
Страница 49: ...Page 49 Notes...
Страница 50: ...Page 50 Notes...
Страница 51: ...Page 51 Notes...
Страница 52: ...P N 41093 Rev E 9 06...