MAINTENANCE INSTRUCTIONS
45
P
ARAMETER
7
–
C
ENTRAL HEATING PUMP OVERRUN TIMER
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter
within the prescribed limits
00 = 0 x 5 sec = 0 sec
90 = 90 x 5 sec = 450 sec (7.5 min)
The default value is 36 = 180 sec = 3 min
7. Press and release button ‘S’ to confirm. The parameter
number (7) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER
8
–
D.H.W
PUMP OVERRUN TIMER
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter
within the prescribed limits
00 = 0 x 5 sec = 0 sec
90 = 90 x 5 sec = 450 sec (7.5 min)
The default value is 18 = 90 sec = 1.5 min
7. Press and release button ‘S’ to confirm. The parameter
number (8) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER NO
.9
Not applicable for premix burner (only for atmospheric burner)
P
ARAMETER NO
.10
Not applicable for premix burner (only for atmospheric burner)
P
ARAMETER NO
.11
Not applicable for premix burner (only for atmospheric burner)
P
ARAMETER NO
.12
Not applicable for premix burner (only for atmospheric burner)
P 07
S
S
S
S
36
18
P 08
110V 60Hz
110V 60Hz
110V 60Hz
110V 60Hz
Содержание PCC 34-H
Страница 8: ...GENERAL INFORMATION 5 ...
Страница 9: ...GENERALInformation 6 ING ...
Страница 10: ...GENERALInformation 7 ...
Страница 11: ...GENERALInformation 8 ...
Страница 32: ...INSTALLATION INSTRUCTIONS 29 Venting Pictures Illustrations ...
Страница 33: ...INSTALLATION INSTRUCTIONS 30 Included With Each Combination Boiler Is A PAHVK Horizontal Kit ...
Страница 37: ...INSTALLATION INSTRUCTIONS 34 ...
Страница 38: ...INSTALLATION INSTRUCTIONS 35 ...
Страница 67: ...INSTALLATION INSTRUCTIONS 64 INDIRECT FIRED WATER HEATER 6 9 D H W sensor connection ...
Страница 71: ...68 6 13 Cycle Sequence of Operations ...
Страница 72: ...69 Pensotti LLC 34 Coffin Ave Brewer ME 04412 P 207 942 3636 F 207 942 3737 www pensottiboiler com ...