32
Modbus Registers
Description
40001
Heart Beat register. Simply a counter that is increment
every second to indicate the analyzer is operating properly
The counter overflows to 0 after 65535 (approx 18 hours)
40002
Spare not used. Value read would be 0
40003
Current analyzer mode. Values are:
1
Analyzer in warmup time
2
Purge or clear Cycle
3
Sampling Cylce
4
Calibration Mode
40004
Elapsed time in seconds of current mode
40005
H2S reading of the last sample cycle.
Typical sampling time every 180 seconds. This register is
therefore, updated every 180 seconds.
( *see note 1)
40006
Current CO2 Reading
40007
H2S Low Alarm Level
( *see note 1)
40008
H2S High Alarm Level
( *see note 1)
40009
CO2 Low Alarm Level
( *see note 1)
400010
CO2 High Alarm Level
( *see note 1)
Continue on next page
Note 1
: The value in this register is multiple of 10. In other words value 120 is
actually 12.0 similarly 25 means 2.5.
The PLC should b programmed so that value read is divided by 10 to get the
actual reading.