ECP
300
EXPERT STEPPER
Page 24
OPERATION AND MAINTENANCE MANUAL
Rev. 01-20
in1
INP-1 digital input setting
17 = tPF % fixed opening (N.O.)
16 = Compressor protection, display only (N.O., EcA)
15 = Condenser fan protection, display only (N.O., EFc)
14 = Evaporator fan protection, display only (N.O., EFE)
13 = Oil pressure switch protection (N.O., EcO)
12 = Minimum pressure switch protection (N.O., EcL)
11 = Maximum pressure switch protection (N.O., EcH)
10 = Pressure switch protection (N.O., EcP)
9 = Compressor thermal protection (N.O., Ect)
8 = Night input (energy saving) (N.O.)
7 = Remote defrost stop (N.O., active on the ascent front)
6 = Start defrosting remotely (N.O., active on the ascent front)
5 = Remote standby (N.O.) To indicate the remote standby OFF is
displayed on the display
4 = Pump-down pressure switch (N.O.)
3 = Man in Cell alarm (N.O.)
2 = Compressor protection (N.O.)
1 = Door switch (N.O.)
0 = Disabled
-1 = Door switch (N.C.)
-2 = Compressor protection (N.C.)
-3 = Man in Cell Alarm (N.C.)
-4 = Pump-down pressure switch (N.C.)
-5 = Remote Stand-by (N.C.) To indicate the remote standby OFF
is displayed on the display
-6 = Start defrost remotely (N.C., active on the descent front)
-7 = Stop defrost remotely (N.C., active on the descent front)
-8 = Night input (energy saving) (N.C.)
-9 = Compressor thermal protection (N.C., Ect)
-10 = Pressure switch protection (N.C., EcP)
-11 = Maximum pressure switch protection (N.C., EcH)
-12 = Minimum pressure switch protection (N.C., EcL)
-13 = Oil pressure switch protection (N.C., EcO)
-14 = Evaporator fan protection, display only (N.C., EFE)
-15 = Condenser fan protection, display only (N.C., EFc)
-16 = Compressor protection, display only (N.C., EcA)
-17 = tPF % fixed opening (N.C.)
1
In2
INP-2 digital input setting
As In1
2
In3
INP-3 digital input setting
As In1
3
In4
INP-4 digital input setting
As In1
4
bEE
Buzzer enabling
0 = disabled
1 = enabled
1
P1
Password: security type
(active when PA is other than 0)
0 = displays only the set-point and allows tacit
alarms
1 = displays the set-point, allows tacit alarms, +
defrost + light + aux key + access to variable
only display menu
2 = blocks programming access of 1, 2, 3 and 4
level (all other functions are allowed)
3 = blocks programming access of 2, 3 and 4
levels (all other functions are allowed)
3
PA
Password
(see P1 for type of protection)
0...999
0 = function disabled
0