USER AND MAINTENANCE MANUAL
Rev. 01-19
Air change
The air changes can be enabled with parameter rA. Cyclical air exchange cycles, which
can be set using the rA parameter, can be performed. The duration of the air change is
defined by parameter drA. During air change, hot, cold, humidity and dehumidification do
not activate. It is possible, at any time, to force an air change with the “Air cycle” button.
The “
Air change
” menu can be accessed from the main Configuration page (“Parameters”
Button). The display of this item can be set in the “Password” sub-menu => “Configure
user level menu” and by selecting the “
Air change
” item (installer login required).
Configure PAN
“Configure PAN” allows to select which functions of the PAN control unit are enabled; it
particularly allows the humidity and heat control to be enabled/disabled.
The “
Configure PAN
” menu can be accessed from the main Configuration page
(“Parameters” Button). The display of this item can be set in the “Password” sub-menu =>
“Configure user level menu” and by selecting the “
Configure PAN
” item (installer login
required).
VARIABLES
MEANING
VALUES
DEFAULT
drA
Air change period.
1 ÷ 10 min
6
rA
Air change interval
00:01 ÷ 24:00
OFF
VARIABLES
MEANING
VALUES
DEFAULT
dEU
Dehumidification mode selection.
Separate dehumidification calls hot and
cold only for temperature.
0 = cooling
1 = heating
2 = separate dehumidification
3 = separate dehumidification and
active when cold output is off
0
EnU
Humidification enabling
0 = disabled 1 = enabled
1
End
Dehumidification enabling
0 = disabled 1 = enabled
1
EnH
Hot enabling
0 = hot disabled 1 = hot enabled
1
EnC
Cold enabling
0 = cold disabled 1 = cold enabled
1
Hr
Humidity management
Hr = 0 humidity management
disabled.
The humidity probe can be connected
without error on the display.
Hr = 1 humidity management enabled.
1
HmV
Minimum
value
of
the
humidifier
regulation analogue output.
0
÷
+99 Rh%
20 Rh%
Air change
Configure PAN
8.3.4