USER AND MAINTENANCE MANUAL
Rev. 01-19
ANALOGUE INPUT CONNECTION ON 100N MASTER3
PIN
TERMINALS
DESCRIPT.
TERMINALS
TYPE OF
SIGNAL
ANALOGUE
INPUT
DEFAULT SETTINGS
ANALOGUE INPUTS
DEFAULT
SETTINGS BRIDGES
ON 100N MASTER3
27
RH
4-20mA
AI1
3 = Ambient humidity
probe
J11=2-3
J12=1-2
J13= open
28
V+
29
NTC
AI2
1 = Ambient temp.
J21=1-2
J22=2-3
J13= open
30
31
NTC
AI3
2 = Evaporator temp.
J31=1-2
J32=2-3
J33= open
32
33
NTC
AI4
0 = Disabled
J41=1-2
J42=2-3
J43= open
34
35
NTC
AI5
0 = Disabled
J51=1-2
J52=2-3
J53= open
36
POSSIBLE CONFIGURATIONS
ANALOGUE INPUTS AI1
÷
AI5
Access menu:
Parameters >Configure I/O
>Analogue inputs
0 = Disabled
1 = Ambient temperature (NTC)
2 = Evaporator temperature (NTC)
3 = Ambient humidity probe (4-20mA)
The selection of the desired function for each
analogue input is done by the configuration of the
dedicated parameter in the “ Parameters > Configure
I/O > analogue inputs” menu combined with the
correct setting of the Hardware configuration jumpers
on the 100N-MASTER3 under the removable front
cover (see the side image).
In particular, the configuration is as follows:
For NTC probes
: J*1=1-2, J*2=2-3, J*3=open
For 4-20mA probes : J*1=2-3, J*2=1-2, J*3=open
*= number analogue input