![Pego 100N MASTER3 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/pego/100n-master3/100n-master3_user-and-maintenance-manual_1521988012.webp)
VISION
TOUCH
PAN
Pag. 12
USER AND MAINTENANCE MANUAL
Rev. 01-19
Following are the electrical connections of the controller divided by type. The
configurations of the inputs and outputs shown below are set by default but can be
changed to suit your needs. The connection between the console and 100N MASTER3
has two possible variants based on the distance between the two components.
POWER SUPPLY AND CONNECTION CONSOLE / 100N MASTER3
1) Connection between the console and 100N MASTER3 with distance within
10m:
CHAPTER 3: ELECTRICAL CONNECTIONS
Power
supply
Connect the ground to the GND
terminal of M2 in the console
(functional ground).
This connection helps to limit the
effects of the electromagnetic
noise on the control system.
The earth connection must be
made in a manner consistent with
applicable regulations.
Connect the power to terminals 1
and 2 of 100N MASTER3.
Switching power supply:
115÷230Vac ±10% 50/60Hz
Demand: 20 VA max.
.
Use the supplied telephone cord
and connect the 8-pin Plugs to
J1in the console and to J1 in the
100N MASTER3 (it includes
communication and power).
Power
supply
3.1