USER AND MAINTENANCE MANUAL
Rev. 01-19
Process adjustment
“Process adjustment” allows setting the differentials and the temperature and humidity
neutral area of the PAN.
The “
Process adjustment
” menu can be accessed from the main Configuration page
(“Parameters” Button). The display of this item can be set in the “Password” sub-menu =>
“Configure user level menu” and by selecting the “Process adjustment” item (installer login
required).
VARIABLES
MEANING
VALUES
DEFAULT
dtC
HOT temperature differential
with reference to main SET-
POINT. It is expressed in absolute value and it defines the
temperature hysteresis for HOT referred to the temperature
SET-POINT.
(dnC+0,2) ÷ 10,0 °C
2,0 °C
dtF
COLD temperature differential
with reference to main
SET-POINT. It is expressed in absolute value and it defines
the temperature hysteresis for COLD referred to the
temperature SET-POINT.
(dnF+0,2) ÷ 10,0 °C
2,0 °C
dnC
Neutral hot zone
Neutral temperature zone refers to the
main setpoint. Hot and cold are not activated in a neutral
zone. It refers to the lower part (hot) in relation to the
temperature setpoint.
0,0 ÷ (dtC-0,2) °C
0,0 °C
dnF
Neutral cold zone
Neutral temperature zone refers to the
main setpoint. Cold and hot are not activated in a neutral
zone. It refers to the upper part (cold) in relation to the
temperature setpoint.
0,0 ÷ (dtF-0,2) °C
0,0 °C
dUU
HUMIDIFICATION differential
with reference to humidity
SET-POINT. It is expressed in absolute value and it defines
the humidification hysteresis referred to the humidity SET-
POINT.
(dnU+1) ÷ 10 rH%
5 rH%
dUd
DEHUMIDIFICATION differential
with reference to humidity
SET-POINT. It is expressed in absolute value and it defines
the dehumidification hysteresis referred to the humidity SET-
POINT.
(dnd+1) ÷ 10 rH%
5 rH%
dnU
NEUTRAL humidification zone
with reference to the main
SETPOINT. Humidification and dehumidification are not
activated in a neutral zone. This includes the lower part
(humidification) in relation to the humidity SETPOINT.
0 ÷ (dUU-1) rH%
0 rH%
dnd
NEUTRAL dehumidification zone
with reference to the
main SETPOINT. Humidification and dehumidification are
not activated in a neutral zone. This includes the upper part
(dehumidification) in relation to the humidity SETPOINT.
0 ÷ (dUd-1) rH%
0 rH%
StC
Temperature setpoint (hot manual mode)
When you activate the "hot manual mode", this value is
loaded into the temperature setpoint.
LSh ÷ HSh °C
27,0 °C
SUC
Humidity setpoint (hot manual mode)
When you activate the "hot manual mode", this value is
loaded into the humidity setpoint.
0 ÷ 100 rH%
80 rH%
StF
Temperature setpoint (cold manual mode)
When you activate the "cold manual mode", this value is
loaded into the temperature setpoint.
LSc ÷ HSc °C
-5,0 °C
Process regulation
8.3.1