For the correct management of the plant, it will be the responsibility of the installer to use
the defrost output, that must allow the opening of the cycle inversion electrovalve and the
closing of the liquid electrovalve.
For the capillary plants (without thermostatic valve) it is sufficient to control the cycle
inversion electrovalve using the defrosting relay control.
Ventilation
The parameters of the Ventilation menu allow to set the management of the fans in the
various operating modes. The “
Ventilation
” menu can be accessed from the main
Configuration page (“Parameters” Button). The display of this item can be set in the
“Password” sub-menu => “Configure user level menu” and by selecting the “
Ventilation
”
item (installer login required).
VARIABLES
MEANING
VALUES
DEFAULT
F5
Fan pause
after defrost (minutes)
Allows to keep the fans stopped for a time
F5
after dripping.
This time starts counting from the end of dripping. If dripping is
not set, at the end of defrost the fans pause immediately.
0 ÷ 10 min
0 min
F3c
Fan status when cold, hot, humidification and
dehumidification are stopped (Cold manual mode)
0 = Fans running
constantly
1 = Fans off if cold, hot,
humidification and
dehumidification off
1
F3h
Fan status when cold, hot, humidification and
dehumidification are stopped (Hot manual mode)
0 = Fans running
constantly
1 = Fans off if cold, hot,
humidification and
dehumidification off
0
F4
Fan pause during defrost
0 = Fans running during
defrost
1 = Fans not running
during defrost
1
F6
Evaporator fans activation for air circulation
.
The fans are activated for a time defined by F7 if they were
not switched on for the time F6.
If the time of activation coincides with the defrost phase, it
waits for the end of defrost.
The fan speed (high/low) is the same as that selected for the
phase in progress.
OFF / 1
÷
240 min
OFF
F7
Evaporator fans activation period for air circulation.
Time fans running for air circulation (F6).
0
÷
240 sec
10 sec
F8
Fan speed
.
The value of this variable changes based on the
setting made in the last phase of a program carried out.
0 = High speed
1 = Low speed
0
EFa
Enables 0-10V output for fan speed control
The digital outputs high and low fan speed becomes the
enable. (Them Turned on if the 0-10V output higher than 0V)
0 = disabled
1 = enabled
0
Fs
Fan speed (percentage) when EFa=1.
The value of this variable changes based on the setting made
in the last phase of a program carried out.
20 ÷ 100 %
100%
Fans
8.3.3